Text |
2009-07-24 19:21:51 | |
| ** DENIED ** |
| |
| 1) NOTE: PLEASE COORDINATE ALL PLANS SUBMITTED. PLEASE |
| SEE THAT TWO SET OF PLANS SUBMITTED CONTAIN ELECTRICAL |
| AND PLUMBING PLANS FROM TWO DIFFERENT SUITES OR UNITS. |
| FOR EXAMPLE ONE SET CONTAINS ELECTRICAL SHEETS FOR UNIT |
| 104-B AND THE OTHER FOR SUITE 205. |
| AS THE PERMIT APPLICATION IS APPLYING FOR WORK IN UNIT |
| 205 THE ELECTRICAL REVIEW WILL BE DONE FOR 205. |
| |
| |
| 2) NOTE: PLEASE SEE THAT THE SUBMITTED WHOLE BUILDING |
| METHOD A CALCULATIONS MAY NOT BE USED. THIS IS A TENANT |
| BUILDING OUT AND NOT A WHOLE BUILDING BY THE |
| DEFINITIONS SET FORTH IN CHAPTER 13 SECTION 202 OR |
| CHAPTER 2 OF THE FBC. |
| PLEASE SEE 13-415.AB.5. |
| THE PLANS SUBMITTED ALSO CONTAIN LIGHTING CALCULATIONS |
| PER SECTIONS STATED FROM THE 2004 FBC. . |
| IT IS ALSO NOT PERMISSIBLE TO USE TWO DIFFERENT METHODS |
| OF CALCULATIONS. |
| PLEASE SEE TABLE ON SHEETS AS HALL AREA STATES A |
| WATTAGE TOTAL OF 116 YET BASED ON THE WATTAGE OF THE |
| FIXTURES ON THE IDR OF THE SUBMITTED ENERGY |
| CALCULATIONS THIS IS NOT POSSIBLE. THE IDR STATES 2-64 |
| WATT FIXTURES WHICH WOULD BE 128WATTS AND NOT THE 116 |
| AS STATED ON PLANS. THIS WOULD NOT COORDINATE WITH THE |
| FIXTURES NOTES. |
| PLEASE SEE OTHER ROOMS AND AREAS AND THE ALLOWANCES |
| UNDER THE 2007 FBC WITH THE 2009 REVISIONS. |
| THE IDR ALSO INDICATES MANUAL ON/OFF WHICH IS NOT WHAT |
| IS ON PLANS. |
| |
| 3) NOTE: THE PLANS STATE THE 2007 FBC HOWEVER AS |
| ADOPTED THE 2007 FBC WITH THE 2009 REVISIONS HAS |
| SUBSTANTIAL CHANGES OVER THE 2007 FBC. |
| |
| *** AS PLANS ARE NO LONGER RELEASED TO CONTRACTOR PER |
| THE NEW BUILDING DIRECTOR, ONCE CORRECTIONS ARE MADE |
| INSERTION OF NEW SHEETS AND DOCUMENTS WILL NEED TO TAKE |
| PLACE IN THIS DEPARTMENT. |
| |
| |
| |
| IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| CONTACT THIS REVIEWER. |
| |