 1) NOTE: PLEASE COORDINATE ALL PLANS SUBMITTED. PLEASE
 SEE THAT TWO SET OF PLANS SUBMITTED CONTAIN ELECTRICAL
 AND PLUMBING PLANS FROM TWO DIFFERENT SUITES OR UNITS.
 FOR EXAMPLE ONE SET CONTAINS ELECTRICAL SHEETS FOR UNIT
 104-B AND THE OTHER FOR SUITE 205.
 AS THE PERMIT APPLICATION IS APPLYING FOR WORK IN UNIT
 205 THE ELECTRICAL REVIEW WILL BE DONE FOR 205.
  
  
 2) NOTE: PLEASE SEE THAT THE SUBMITTED WHOLE BUILDING
 METHOD A CALCULATIONS MAY NOT BE USED. THIS IS A TENANT
 BUILDING OUT AND NOT A WHOLE BUILDING BY THE
 DEFINITIONS SET FORTH IN CHAPTER 13 SECTION 202 OR
 CHAPTER 2 OF THE FBC.
 PLEASE SEE 13-415.AB.5.
 THE PLANS SUBMITTED ALSO CONTAIN LIGHTING CALCULATIONS
 PER SECTIONS STATED FROM THE 2004 FBC. .
 IT IS ALSO NOT PERMISSIBLE TO USE TWO DIFFERENT METHODS
 OF CALCULATIONS.
 PLEASE SEE TABLE ON SHEETS AS HALL AREA STATES A
 WATTAGE TOTAL OF 116 YET BASED ON THE WATTAGE OF THE
 FIXTURES ON THE IDR OF THE SUBMITTED ENERGY
 CALCULATIONS THIS IS NOT POSSIBLE. THE IDR STATES 2-64
 WATT FIXTURES WHICH WOULD BE 128WATTS AND NOT THE 116
 AS STATED ON PLANS. THIS WOULD NOT COORDINATE WITH THE
 FIXTURES NOTES.
 PLEASE SEE OTHER ROOMS AND AREAS AND THE ALLOWANCES
 UNDER THE 2007 FBC WITH THE 2009 REVISIONS.
 THE IDR ALSO INDICATES MANUAL ON/OFF WHICH IS NOT WHAT
 IS ON PLANS.
  
 3) NOTE: THE PLANS STATE THE 2007 FBC HOWEVER AS
 ADOPTED THE 2007 FBC WITH THE 2009 REVISIONS HAS
 SUBSTANTIAL CHANGES OVER THE 2007 FBC.
  
 *** AS PLANS ARE NO LONGER RELEASED TO CONTRACTOR PER
 THE NEW BUILDING DIRECTOR, ONCE CORRECTIONS ARE MADE
 INSERTION OF NEW SHEETS AND DOCUMENTS WILL NEED TO TAKE
 PLACE IN THIS DEPARTMENT.
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  