Plan Review Notes For Permit 09070265
Permit Number 09070265
Review Stop G
Sequence Number 2
Notes
Date Text
2009-08-13 14:25:55DENIED
 REFERENCE:
 FBC-2004 RESIDENTIAL
 FBC-2004 CHAPTER 1
  
 ****FROM PREVIOUS REVIEW
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2007 RESIDENTIAL OR
 2007 FUEL GAS CODE. -- THE EXISTING PIPING OUT OF THE
 METER AND LOCATION OF THE TEE TO THE EXISTING
 APPLIANCES, PIPE SIZE AS WELL AS PIPE MATERIAL SHALL BE
 SHOWN ON THE ISOMETRIC.
 ****RESPONSE NOTED, BUT PLEASE INDICATE WHAT GRC PIPE
 IS. SUBMIT MANUF SPECIFICATIONS FOR THE MATERIAL TO
 VERIFY APPROVAL OF THE MATERIAL. SECTION G2414.
  
 2. TYPE OF GAS, (LP OR NATURAL). -- PLANS INDICATE
 NATURAL GAS, BUT THE APPLICATION STATES "INSTALLATION
 OF GAS TANK". PLEASE CLARIFY. SECTION 106.1.1.
 ****NO RESPONSE, COMMENT NOT ADDRESSED.
  
 3. OK
  
 4. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
 ****NO RESPONSE, APPLICATION STILL INDICATES GAS TANK,
 BUT PLANS STATE NATURAL GAS. PLEASE CLARIFY.
  
 5. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND
 APPURTENANCES PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
 ****NO RESPONSE, APPLICATION STILL INDICATES GAS TANK,
 BUT PLANS STATE NATURAL GAS. PLEASE CLARIFY.
  
 ********NEW COMMENT********
  
 1B. PIPING DIAGRAM SHOWS A REGULATOR AT THE NEW
 GENERATOR, BUT IS NOT INDICATED AT THE DRYER OR WATER
 HEATER. PLEASE INDICATE WHERE THE REGULATOR(S) ARE FOR
 THE EXISTING APPLIANCES. A LISTED SHUT OFF VALVE SHALL
 BE INSTALLED IMMEDIATLY AHEAD OF EACH REGULATOR.
 SECTION G2420.4.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  