Plan Review Notes
Plan Review Notes For Permit 09070265
Permit Number 09070265
Review Stop E
Sequence Number 1
Notes
Date Text
2009-07-15 12:15:59 
 ** DENIED **
  
 1) NOTE: PLEASE SHOW DIMENSIONS ON ELECTRICAL SITE
 PLANS FOR CLEARANCES FROM HOUSE. THE LOCATIONS ARE
 NOTED HOWEVER SITE/SURVEY FINAL PLANS NEED TO SHOW A
 RECORD OF THE EXACT LOCATION UNIT WILL BE PLACED.
 110.26, NFPA_37
  
 2) NOTE: PLAN SUBMITTED FOR SLAB DETAIL IS A PHOTO-COPY
 OF AN ENGINEER PLAN. PLEASE KNOW THAT THE TITLE BLOCK,
 SIGNATURE, DATE AND SEAL WOULD BE REQUIRED FROM THAT
 ENGINEER WHEN USING THEIR PLAN OR DETAIL. FS
 471.025,FAC 61G15-23.002
 WHEN MEETING EXCEPTIONS DESIGN MAY BE UNDER FS 489.
  
 3) NOTE: PLEASE SHOW OR PROVIDE INFORMATION OF THE LOAD
 SHEDDING OF HEAT STRIPS ON THE STAND-BY SYSTEM. PLANS
 STATE THE ASSUMED LOAD FOR A/C CONDENSING UNITS,
 HOWEVER IF AUTOMATIC TRANSFER IS TAKING PLACE. THE LOAD
 FOR HEAT MUST ALSO BE FIGURED UNLESS LOAD SHEDDING.
 702.5
 PLANS DO MENTION LOAD SHEDDING OF NON-ESSENTIAL LOADS
 HOWEVER UNCLEAR HOW HEAT ON A/C SYSTEM IS UNDER THIS.
  
 4) NOTE: WHEN MEETING 702.11 THEN SIGNAGE IS REQUIRED
 AT THE SERVICE LOCATION AS WELL AS MAIN HOUSE SERVICE
 LOCATION AS TO THE DISCONNECTING MEANS FOR THE STAND-BY
 POWER.
 225.37, 230.2E
  
  
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  