2009-07-15 12:15:59 | |
| ** DENIED ** |
| |
| 1) NOTE: PLEASE SHOW DIMENSIONS ON ELECTRICAL SITE |
| PLANS FOR CLEARANCES FROM HOUSE. THE LOCATIONS ARE |
| NOTED HOWEVER SITE/SURVEY FINAL PLANS NEED TO SHOW A |
| RECORD OF THE EXACT LOCATION UNIT WILL BE PLACED. |
| 110.26, NFPA_37 |
| |
| 2) NOTE: PLAN SUBMITTED FOR SLAB DETAIL IS A PHOTO-COPY |
| OF AN ENGINEER PLAN. PLEASE KNOW THAT THE TITLE BLOCK, |
| SIGNATURE, DATE AND SEAL WOULD BE REQUIRED FROM THAT |
| ENGINEER WHEN USING THEIR PLAN OR DETAIL. FS |
| 471.025,FAC 61G15-23.002 |
| WHEN MEETING EXCEPTIONS DESIGN MAY BE UNDER FS 489. |
| |
| 3) NOTE: PLEASE SHOW OR PROVIDE INFORMATION OF THE LOAD |
| SHEDDING OF HEAT STRIPS ON THE STAND-BY SYSTEM. PLANS |
| STATE THE ASSUMED LOAD FOR A/C CONDENSING UNITS, |
| HOWEVER IF AUTOMATIC TRANSFER IS TAKING PLACE. THE LOAD |
| FOR HEAT MUST ALSO BE FIGURED UNLESS LOAD SHEDDING. |
| 702.5 |
| PLANS DO MENTION LOAD SHEDDING OF NON-ESSENTIAL LOADS |
| HOWEVER UNCLEAR HOW HEAT ON A/C SYSTEM IS UNDER THIS. |
| |
| 4) NOTE: WHEN MEETING 702.11 THEN SIGNAGE IS REQUIRED |
| AT THE SERVICE LOCATION AS WELL AS MAIN HOUSE SERVICE |
| LOCATION AS TO THE DISCONNECTING MEANS FOR THE STAND-BY |
| POWER. |
| 225.37, 230.2E |
| |
| |
| |
| ** IMPORTANT ** |
| ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| INTO TWO SETS/FOLDERS/BINDERS ETC. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| ANY DELAYS. |
| |
| IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| CONTACT THIS REVIEWER. |
| |