Date Text
2009-07-24 12:04:43*****APPROVED*****
  
 THE APPROPIATE SITE PLAN, APPROVED BY FIRE MARSHAL
 CARSILLO ON 7/14/2009, WAS STAMPED, INITIALED, AND
 DATED.
2009-07-14 13:35:57ACCORDING TO PERMIT APPLICATION "REMOVE ELECTRIC AND
 REINSTALL AFTER FIRE PRROFING WALL.
  
 1. THE REMOVAL OF ELECTRICAL CIRUITS AND FIXTURES SHALL
 COMPLY WITH NFPA 70, THE STANDARD FOR ELECTRICAL SAFETY
 REQUIREMENTS FOR EMPLOYEE WORKPLACES.
  
 2. THE REINSTALLATION OF ELECTRICAL CIRCUITS AND
 FIXTURES SHALL COMPLY WITH NFPA 70, THE NATIONAL
 ELECTRICAL CODE.
  
 3. ALL ILLUMINATED EXIT SIGNS AND EMERGENCY LIGHT
 FIXTURES SHALL BE IN GOOD WORKING ORDER.
  
 4. ALL ELECTRICAL WORK SHALL BE PERFORMED BY A LICENSED
 QUALIFIED ELECTRICIAN.
  
 5. ALL WORK IS SUBJECT TO FIELD INSPECTION AND
 APPROVAL.
  
 6. ALL WORK IS TO BE INSPECTED BY THE CITY OF WEST PALM
 BEACH ELECTRICAL DIVISION.
  
  
 APPROVED PROVISO:
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
 804-4709 PHONE
 804-4774 FAX
  