Plan Review Notes
Plan Review Notes For Permit 09070229
Permit Number 09070229
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2009-07-30 11:30:57*****PROVISO*****
  
  
 AS TO BE DISCUSSED WITH THE WEST PALM BEACH BUILDING
 OFFICIAL AND RELAYED TO THE PROJECT MANAGER/DEVELOPER,
 ANY REVISION(S) TO THIS PLAN SET AND/OR ANY OTHER
 FUTURE PLAN SUBMITTALS FOR THE OAKTON COMMONS PROJECT
 SHALL INCLUDE THE FOLLOWING CORRECTION(S) OR
 ADDENDUM(S) FOR FIRE PLAN REVIEW'S APPROVAL:
  
 1. ON SHEET LP-1, THE FIRE HYDRANT SHOWN AT THE
 SOUTHWEST CORNER OF THE BUILDING SHOULD HAVE THE
 4"/4.5"OUTLET (STEAMER CAP) FACING THE ROADWAY (FOXTAIL
 VIEW COURT).
  
 2. ONLY FOR BUILDINGS WHICH CONTAIN 3 OR MORE DWELLING
 UNITS UNDER A COMMON ROOF, NFPA 101 - LIFE SAFETY CODE
 - 2006 EDITION SHALL BE REFERENCED. ADD TO CODE SECTION
  
 3. SHOW THE LOCATION OF THE 2A:10BC RATED FIRE
 EXTINGUISHER(S) THAT SATISFY THE 75 ' TRAVEL DISTANCE.
 THIS MAY BE ACCOMPLISHED ONE OF TWO WAYS: 1) PROVIDE AN
 ENCLOSED/PROTECTED FIRE EXTINGUISHER ON THE EXTERIOR
 ELEVATION COMMON TO THE BUILDING OR BETTER YET 2) THE
 PLACEMENT OF FIRE EXTINGUISHER(S) INSIDE EACH
 INDIVIDUAL DWELLING UNIT.
  
 4. ON SHEET A-3.1, FRONT ELEVATION, DISPLAY/SHOW THE
 ACTUAL NUMERICAL ADDRESS NUMBER FOR EACH UNIT. AS PER
 WEST PALM BEACH CODE, THE NUMBERS SHALL BE NO LESS THAN
 3" IN HEIGHT AND NO LESS THAN 1" IN WIDTH/STROKE.
  
 5. ON SHEETS E1.0 THRU E-1.4, ADD THE FOLLOWING VERBAGE
 AS PER FLORIDA STATUTE 553:885: " AN OPERATIONAL CARBON
 MONOXIDE (CO) ALARM SHALL BE INSTALLED WITHIN 10 FEET
 OF EACH ROOM USED FOR SLEEPING PURPOSES." IT APPEARS
 THAT THE CO DETECTOR SHOWN ON THE SECOND FLOOR OF THE
 DWELLING UNITS CAN BE BETTER CENTERED/ALIGNED TO ATTAIN
 THE DISTANCE REQUIREMENT.
  
 PLAN SHEETS TU-1.0, TU-1.1, TU-2.0, TU-2.1, TU-3.0,
 A-3.1, E-1.0, E1.1, E1.2, E-1.3, AND E-1.4 WERE
 STAMPED, INITIALED, AND DATED.
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722
 FIRE PREVENTION BUREAU
 561-804-4724