2009-07-30 11:27:57 | *****PROVISO***** |
| |
| |
| AS TO BE DISCUSSED WITH THE WEST PALM BEACH BUILDING |
| OFFICIAL AND RELAYED TO THE PROJECT MANAGER/DEVELOPER, |
| ANY REVISION(S) TO THIS PLAN SET AND/OR ANY OTHER |
| FUTURE PLAN SUBMITTALS FOR THE OAKTON COMMONS PROJECT |
| SHALL INCLUDE THE FOLLOWING CORRECTION(S) OR |
| ADDENDUM(S) FOR FIRE PLAN REVIEW'S APPROVAL: |
| |
| 1. ON SHEET LP-1, THE FIRE HYDRANT SHOWN AT THE |
| SOUTHWEST CORNER OF THE BUILDING SHOULD HAVE THE |
| 4"/4.5"OUTLET (STEAMER CAP) FACING THE ROADWAY (FOXTAIL |
| VIEW COURT). |
| |
| 2. ONLY FOR BUILDINGS WHICH CONTAIN 3 OR MORE DWELLING |
| UNITS UNDER A COMMON ROOF, NFPA 101 - LIFE SAFETY CODE |
| - 2006 EDITION SHALL BE REFERENCED. ADD TO CODE SECTION |
| |
| 3. SHOW THE LOCATION OF THE 2A:10BC RATED FIRE |
| EXTINGUISHER(S) THAT SATISFY THE 75 ' TRAVEL DISTANCE. |
| THIS MAY BE ACCOMPLISHED ONE OF TWO WAYS: 1) PROVIDE AN |
| ENCLOSED/PROTECTED FIRE EXTINGUISHER ON THE EXTERIOR |
| ELEVATION COMMON TO THE BUILDING OR BETTER YET 2) THE |
| PLACEMENT OF FIRE EXTINGUISHER(S) INSIDE EACH |
| INDIVIDUAL DWELLING UNIT. |
| |
| 4. ON SHEET A-3.1, FRONT ELEVATION, DISPLAY/SHOW THE |
| ACTUAL NUMERICAL ADDRESS NUMBER FOR EACH UNIT. AS PER |
| WEST PALM BEACH CODE, THE NUMBERS SHALL BE NO LESS THAN |
| 3" IN HEIGHT AND NO LESS THAN 1" IN WIDTH/STROKE. |
| |
| 5. ON SHEETS E1.0 THRU E-1.4, ADD THE FOLLOWING VERBAGE |
| AS PER FLORIDA STATUTE 553:885: " AN OPERATIONAL CARBON |
| MONOXIDE (CO) ALARM SHALL BE INSTALLED WITHIN 10 FEET |
| OF EACH ROOM USED FOR SLEEPING PURPOSES." IT APPEARS |
| THAT THE CO DETECTOR SHOWN ON THE SECOND FLOOR OF THE |
| DWELLING UNITS CAN BE BETTER CENTERED/ALIGNED TO ATTAIN |
| THE DISTANCE REQUIREMENT. |
| |
| PLAN SHEETS TU-1.0, TU-1.1, TU-2.0, TU-2.1, TU-3.0, |
| A-3.1, E-1.0, E1.1, E1.2, E-1.3, AND E-1.4 WERE |
| STAMPED, INITIALED, AND DATED. |
| |
| CAPT. MICHAEL A. WILLIAMS |
| FIRE PLAN REVIEW |
| 561-805-6722 |
| FIRE PREVENTION BUREAU |
| 561-804-4724 |