2009-08-13 14:36:2709070170
 4047 OKEECHOBEE BLVD., SUITE 230
 "PRE-INSPECT, CHANGE OF OCCUPANCY"
  
 1. PLEASE DECLARE NEW OCCUPANCY TYPE.
  
 2. PLEASE DECLARE INTERIOR FINISH CLASSIFICATIONS FOR
 WALLS AND CEILINGS.
  
 3. PLEASE DECLARE ALL DOOR HARDWARE AND ANY LOCKING
 DEVICES ON EXIT DOORS.
  
 4. PLEASE PROVIDE AN OCCUPANT LOAD FOR SUITE 230.
  
 5. NO DETAIL FOR WALL CONSTRUCTION.
  
 6. PLEASE PROVIDE DETAILS FOR KIDS ROOM, AGE OF
 CHILDREN, HOURS OF OPERATION, AND SUPERVISION.
  
 7. PLEASE INDICATE LOCATIONS OF FIRE EXTINGUISHERS.
  
 8. PLEASE PROVIDE INFORMATION ON EXIT DOOR THAT SWINGS
 INWARD TO LOBBY.
  
 9. PLEASE PROVIDE DETAILS REGARDING EXISTING FIRE
 SPRINKLER SYSTEM. SEPARATE PLANS AND PERMITS REQUIRED
 FOR ANY FIRE SPRINKLER REMODEL.
  
 10. PLANS DO NOT ILLUSTRATE ANY MECHANICAL, ELECTRICAL,
 OR PLUMBING CONTAINED WITHIN BUILDING.,
  
 DENIED
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
 804-4709 PHONE
 804-4774 FAX
  