| ** DENIED REVIEW ** |
| |
| 1) NOTE: PLEASE SUBMIT PLANS CONTAINING MINIMUM DESIGNS |
| FOR THE NEW USE AND OCCUPANCY OF THE LOCATION. THE |
| SUBMITTED LAYOUT DOES NOT INCLUDE ANY INFORMATION ON |
| OCCUPANCY OF ALL LOCATIONS, DESIGN CODES, RATINGS, |
| LIGHTING ETC. |
| PLEASE BE SURE TO SEE FBC 2007 W/2009 REVISIONS. |
| PLEASE SEE NFPA-70 2005 |
| PLEASE SEE NFPA-101 2006 LIFE SAFETY CODE. |
| |
| 2) NOTE: PLEASE COMPLY WITH THE REQUIREMENTS CHANGE IN |
| OCCUPANCY UNDER FBC CHAPTER 13. PLEASE SEE 13-101.3, |
| 13-415.AB.1.1,.1.2, .1.3, 13-415.AB.5, 13-415.B ETC |
| |
| 3) NOTE: PLEASE BE SURE TO SHOW ALL CIRCUITING FOR |
| NEW/EXISTING ELECTRICAL WITH ELECTRICAL PANELS, |
| EQUIPMENT, SERVICE MEETING CURRENT CODES OR BEING |
| BROUGHT UP TO CODE. |
| PLEASE SEE NEC, 220,310,300,408,110.26. |
| ALL CODES AND SECTIONS GIVEN IN GENERAL AS PLANS DO NOT |
| SHOW ENOUGH INFORMATION FOR REVIEW FOR CODE COMPLIANCE. |
| |
| 4) NOTE: PLEASE BE SURE TO SEE CHAPTER 11 OF THE FBC |
| FOR ADA COMPLIANCE FOR ANY ITEMS SUCH AS FIRE ALARM |
| DEVICES, CONTROLS, SIGNALS ETC |
| SEE 11-4.27.1, .2 AND .3 |
| |
| 5) NOTE: PLEASE SEE NFPA-101 7.8, 7.9 FOR EGRESS |
| LIGHTING MINIMUMS. PLEASE BE SURE TO SEE NEC 700.12F |
| FOR CIRCUITING TO LOCAL LIGHTING BRANCH CIRCUIT(S). |
| |
| |
| IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| CONTACT THIS REVIEWER. |
| |