2009-07-09 10:55:40RESIDENTIAL (R3) RE-ROOF, BUILDING REVIEW CHECKLIST.
 2007 FL. RESIDENTIAL CODE WITH 2009 REVISIONS.
  
 1- PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS (2
 COPIES) AS REQUIRED BY GENERAL LIMITATION #7 ON LAST
 PAGE OF NOA 07-1203.01 SUBMITTED FOR NAIL ENHANCING AT
 PERIMETER AND CORNER AREAS.
 ***NOTE: DESIGN PROFESSIONAL TO TAKE INTO CONSIDERATION
 THAT THIS BUILDING IS LOCATED IN EXPOSURE "C" WHEN
 DOING THE RAS 117 CALCULATIONS. SEE 2009 REVISIONS
 REGARDING BUILDING EXPOSURE SEC. R301 OF 2007 FLORIDA
 RESIDENTIAL CODE.
  
 2- NOA 07-1203.01 SUBMITTED IS SUPERSEDED ACCORDING TO
 MIAMI-DADE WEBSITE. SEE ATTACHED COPY. USE NOA
 09-0224.01 WHICH IS THE ONE THAT SUPERSEDES NOA
 07-1203.01.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712