Plan Review Notes For Permit 09070068 |
Permit Number |
09070068 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2009-07-08 08:55:07 | ****CORRECTIONS**** | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | FBC FLORIDA BUILDING CODE 2007 | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | | | 1. THE APPLICATION STATES YOU ARE INSTALLING A WINDOW; | | THE PRODUCT APPROVAL SUBMITTED IS FOR A SHUTTER. | | CLARIFY SCOPE OF WORK. FLORIDA STATE OR LOCAL PRODUCT | | APPROVALS REQUIRED FOR EACH OF THE COMPONENT & CLADDING | | ITEMS YOU ARE TO INSTALL, FAC9B72. | | | | 2. PROVIDE A FLOOR PLAN SHOWING LOCATION OF PROPOSED | | IMPROVEMENTS. INCLUDE WINDOW LOCATIONS, SIZES,WINDOW | | TYPE, ROOM DESIGNATIONS AND PROVIDE INFORMATION | | REGARDING THE EXISTING WINDOW (FOR BEDROOMS). FBC R310, | | FBC EB 604.1. THE CLEAR OPENING CANNOT BE REDUCED BY | | MORE THAN 5%. | | | | 3. IF SHUTTERS ARE TO BE INSTALLED, COMPLETE THE SAMPLE | | INSTALLATION SCHEDULE OR PROVIDE ALL INFORMATION TO | | SHOW CODE COMPLIANCE IN ANOTHER FORMAT, FBC*106, FBC | | R301, FBC1609. TWO SETS REQUIRED. THIS FORM IS | | AVAILABLE IN THE LOBBY OR ON THE INTERNET AT | | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/PDF/SCHEDULE_FOR_ | | INSTALLATION.PDF | | | | 4. THE EXPIRED PERMIT WAS FOR A DOOR AND 20 WINDOWS. IS | | THAT WHAT IS TO BE INCLUDED FOR THIS PERMIT? REVISE | | VALUE. | | | | |
|