2009-10-05 13:57:34 | DENIED |
| REFERENCE: |
| FBC-2007 PLUMBING |
| FBC-2007 EXISTING BUILDING |
| FBC-2007 CHAPTER 1 (ADMIN) |
| FBC-2007 CHAPTER 11 |
| |
| 1. PLANS SUBMITTED SHOW A CHANGE IN OCCUPANCY. PER |
| SECTION 906.1 OF THE EXISTING BUILDING CODE, |
| ACCESSIBILITY IN PORTIONS OF BUILDINGS UNDERGOING A |
| CHANGE OF OCCUPANCY CLASSIFICATIONS SHALL COMPLY WITH |
| CHAPTER 11 OF THE FLORIDA BUILDING CODE, BUILDING. |
| SUBMIT A DETAIL SHOWING COMPLIANCE WITH THE FOLLOWING: |
| FOR W/C: |
| A. 11-4.16.2 CLEAR FLOOR SPACE |
| B. 11-4.16.3 HEIGHT |
| C. 11-4.16.4 GRAB BARS |
| D. 11-4.16.5 FLUSH CONTROLS |
| E. 11-4.16.6 DISPENSERS |
| FOR LAVS: |
| A. 11-4.19.2 HEIGHT & CLEARANCES |
| B. 11-4.19.3 CLEAR FLOOR SPACE |
| C. 11-4.19.4 EXPOSED PIPE & SURFACES |
| D. 11-4.19.5 FAUCETS |
| E. 11-4.19.6 MIRRORS |
| FOR TOILET ROOMS: |
| A. 11-4.22.3 TURNING AREA |
| |
| 2. PER TABLE 403.1 OF THE PLUMBING CODE A DRINKING |
| FOUNTAIN IS REQUIRED. PLEASE SHOW THE LOCATION OF THE |
| DRINKING FOUNTAIN AND SUBMIT A DETAIL SHOWING |
| COMPLIANCE WITH SECTION 11-4.15 WITH ALL SUBSECTIONS AS |
| WELL AS SECTION 11-4.1.3(10)(A) PROVISIONS FOR THOSE |
| WHO HAVE DIFFICULTY BENDING OR STOOPING. |
| |
| 3. THE TOTAL VALUE OF THE PROJECT SHALL BE INCLUDED |
| INCLUDING ALL ADDED ROOMS, PLUMBING , ELECTRIC, |
| MECHANICAL ETC. SECTION 108.3. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| ONE SET OF THEM LOOSELY ON TOP OF THE |
| COLLATED PLANS TO BE REVIEWED. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |