Plan Review Notes For Permit 09070059 |
Permit Number |
09070059 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2009-12-04 11:38:19 | *****DENIED***** | | | | | | 1. APPEARING TO BE A CHANGE OF OCCUPANCY, PLEASE | | INDICATE THE NEW OCCUPANCY TYPE (I.E. BUSINESS, | | MERCANTILE, STORAGE, ETC) AND OCCUPANT LOAD IN | | REFERENCE TO THIS PROJECT. | | | | 2. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241- 2004 | | EDITION. | | | | 3. NFPA 101, LIFE SAFETY CODE, 2006 EDITION SHALL BE | | REFERENCED. | | | | 4. PLEASE PROVIDE TRAVEL DISTANCE TO THE EXITS. | | | | 5. SHOW THE LOCATION OF THE EXIT LIGHTS, EMERGENCY | | LIGHTS, AND FIRE EXTINGUISHER(S) FOR THE REMODELED | | FLOOR PLAN. | | | | 6. SPECIFY THE INTERIOR WALL AND CEILING FINISH | | MATERIALS IN TERMS OF CLASS A, CLASS B, OR CLASS C. | | | | 7. SPECIFY THE INTERIOR FLOOR FINISH IN TERMS OF CLASS | | I OR CLASS II. | | | | 8. ARE THE DEVICES SHOWN IN THE ELECTRICAL FLOOR PLAN | | (SHEET A03) SMOKE DETECTORS (SD) OR SMOKE ALARMS (SA) ? | | PLEASE BE ADVISED THAT SMOKE DETECTORS (SD) ARE TIED | | INTO A BUILDING'S FIRE ALARM SYSTEM. | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|