2009-10-11 10:30:09 | |
| ** DENIED REVISION |
| |
| 1) NOTE: A RED-TAG/4 X FEE WAS ISSUED FOR CHANGE IN |
| OCCUPANCY. THIS IS AN EXISTING CODE CASE. |
| THIS PERMIT WAS ISSUED AND APPLIED FOR REPAIR FOR |
| GARAGE DOOR ANCHORS ONLY EVEN THOUGH THESE SAME PLANS |
| WERE PREVIOUSLY SUBMITTED. |
| THIS CAN BE A REVISION HOWEVER PERMIT APPLICATION, |
| VALUE AND SCOPE OF WORK NEEDS TO BE REVISED. THERE IS |
| STILL AN OUTSTANDING 4X FEE DUE FOR CHANGE IN OCCUPANCY |
| WHICH HAS NOT BEEN ADDRESSED. |
| |
| 2) NOTE: PLEASE SEE FBC CHAPTER 13 FOR CHANGES IN |
| OCCUPANCY AND SUBMIT PLANS AND DOCUMENTS ACCORDINGLY. |
| SEE 13-101.3.2. |
| PLEASE SEE EXISTING BUILDING CODE CHAPTER 9 FOR CHANGES |
| IN OCCUPANCY. |
| PLEASE SUBMIT ELECTRICAL PLANS FOR RISER AND OTHER |
| ELECTRICAL SYSTEMS REQUIRED TO MEET FBC CHAPTER 27 |
| WHICH REFERENCES NFPA-70 2005. |
| |
| 3) NOTE: PLEASE SUBMIT COMPLETED PLANS SHOWING ALL |
| CIRCUITING, BRANCH CIRCUITS, PANEL SCHEDULE, RISER |
| DIAGRAM, LOAD CALCULATIONS ETC. |
| AS NO INFORMATION WAS SUBMITTED THERE MAY BE NEW |
| COMMENTS ON THE FOLLOWING REVIEW WHICH CAN NOT BE MADE |
| AT THIS TIME. |
| SEE NEC 210,220,310.16,240.4,408.4, 440.11,.12, 110.26 |
| 700.12 ETC |
| MANY SECTIONS GIVEN IN GENERAL BASED ON THE INCOMPLETE |
| INFORMATION NEEDED. |
| |
| |
| IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| CONTACT THIS REVIEWER. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPARTMENT |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |
| |