2009-07-02 15:45:11RESIDENTIAL (R3) RE-ROOF, BUILDING REVIEW CHECKLIST.
 2007 FL. RESIDENTIAL CODE WITH 2009 REVISIONS.
  
 1- TILE BOND ROOF TILE ADHESIVE NOA 08-0512.18
 SUBMITTED IS GOOD FOR AN ATTACHMENT RESISTANCE OF 31.3
 AS SHOWN ON ROOF TILE NOA 05-0413.01. ACCORDING TO 2009
 REVISIONS TO THE 2007 FLORIDA RESIDENTIAL CODE, THIS
 BUILDING IS LOCATED ON EXPOSURE "C". NEED TO HAVE A
 MINIMUM ATTACHMENT RESISTANCE OF 32.9. THIS ADHESIVE
 DOESN'T WORK FOR THIS BUILDING. PROVIDE TILE ATTACHMENT
 THAT PROVIDE THE MIN. ATTACHMENT RESISTANCE REQUIRED.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER