2009-12-09 15:26:04 | BUILDING PLAN REVIEW |
| PERMIT: 09060761 |
| ADD: 2400 N FLAGLER DRIVE |
| CONT: OCEAN GATE G.C. |
| TEL: (561)644-7446 |
| |
| FL BLD CODE= 2007 FLORIDA BUILDING CODE |
| W/ 2009 FBC SUPPLEMENTS |
| * WEST PALM BEACH AMENDMENTS |
| |
| REST ROOMS: |
| 1) BUILDING PROVISO: |
| BUILDING APPROVED WITH EXCEPTION! |
| THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO |
| CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO |
| INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE |
| ASSESSMENT OF RE-INSPECTION FEE(S). |
| PLEASE PROVIDE ORIGINAL SIGNED AND SEALED SOILS REPORT. |
| 1802.2.1 QUESTIONABLE SOIL. WHERE THE SAFE-SUSTAINING |
| POWER OF THE SOIL IS IN DOUBT, OR WHERE A LOAD-BEARING |
| VALUE SUPERIOR TO THAT SPECIFIED IN THIS CODE IS |
| CLAIMED, THE BUILDING OFFICIAL SHALL REQUIRE THAT THE |
| NECESSARY INVESTIGATION BE MADE. SUCH INVESTIGATION |
| SHALL COMPLY WITH THE PROVISIONS OF SECTIONS 1802.4 |
| THROUGH 1802.6 . |
| |
| 2) BUILDING PROVISO: BUILDING APPROVED WITH EXCEPTION! |
| THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO |
| CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO |
| INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE |
| ASSESSMENT OF RE-INSPECTION FEE(S). |
| |
| FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING, PROVIDE 2 |
| COPIES OF PRODUCT TESTING REPORTS, MISSING REPORTS ARE |
| AS FOLLOWS: |
| A) TRUSS ANCHORS |
| B) GLASS BLOCK |
| C) LOUVERS |
| D) EXTERIOR SWING DOORS |
| E) ROOFING ASSEMBLIES |
| F) ROOF TOP VENT |
| |
| 3) BUILDING PROVISO: WPB ADMIN CODE 106.3* PRODUCT |
| APPROVALS. THOSE PRODUCT WHICH ARE REGULATED BY DCA |
| RULE 9B-72 SHALL BE REVIEWED AND APPROVED IN WRITING BY |
| THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| JURISDICTIONAL APPROVAL. |
| FOUND ON C1.1 THERE IS A ACCESSIBLE RAMP THAT PROVIDES |
| ACCESS TO THE RESTROOMS, THE DESIGN INDICATED IS TO THE |
| FDOT STANDARD, NO SECTIONS ARE PROVIDED FOR THIS ACCESS |
| RAMP, NO BOTTOM LANDING. THE PLANS SHALL BE DESIGNED TO |
| THE FLORIDA BUILDING CODE CHAPTER 11, SECTION 8.1 |
| THROUGH 8.8. THERE ARE NO DETAILS FOUND ON ANY |
| ARCHITECTURAL PLANS. |
| |
| BUILDING PROVISO: FLOOD ZONE A5: MIN ELEVATION: 7'-6". |
| FBC BUILDING 3110.1.2 / CITY OF WPB CODE OF ORDINANCES |
| SECTION 94-546. STRUCTURE IS LOCATED IN AN "A" FLOOD |
| ZONE. A FLOOD ELEVATION CERTIFICATE WILL BE REQUIRED |
| AFTER MONOLITHIC POUR.. |
| |
| JIM WITMER C. B. O. |
| BUILDING PLAN REVIEW II |
| |
| TEL: (561)805-6715 |
| FAX: (561)805-6731 |
| E-MAIL: [email protected] |
| SURVEY: |
| WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES |
| |
| PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| |
| |