2009-07-06 15:11:29 | DENIED |
| REFERENCE: |
| FBC-2007 PLUMBING |
| FBC-2007 CHAPTER 1 |
| FBC-2007 CHAPTER 11 |
| FLORIDA ADMINISTRATIVE CODE |
| FLORIDA STATUTES |
| |
| 1. SHTS DT-1, DT-2, LS-1 THRU LS-4, LD-1, LD-2, LP-1 |
| THRU LP-5 & IR-1 REQUIRES A FIRM LICENSE NUMBER, |
| (CERTIFICATE OF AUTHORIZATION), AND PHONE NUMBER IN THE |
| TITLE BLOCK OF EACH SHEET. ALSO THE DATE THE SIGNATURE |
| AND SEAL ARE AFFIXED SHALL BE INDICATED ON THE SEAL. |
| FAC 61G10-11.010(1)(2) & FS 481.219, 481.306. |
| |
| 2. SHT EP1.0 WASTE RISER DIAGRAM. THE FITTING |
| DOWNSTREAM OF THE WATER CLOSETS DOES NOT GUIDE THE |
| SEWAGE & WASTE IN THE DIRECT OF FLOW AS REQUIRED IN |
| SECTION 706.3. PLEASE CORRECT RISER DIAGRAM. |
| |
| 3. SHT EP1.0 NOTE #1 OF THE WATER RISER. AIR CHAMBERS |
| ARE NOT APPROVED. PLEASE DELETE FROM NOTE. PDI-WH 201. |
| |
| 4. SUBMIT AN ISOMETRIC RISER DIAGRAM FOR THE WATER |
| PIPING. SHOW ALL PIPE SIZES, VALVES ETC. SECTION |
| 106.3.5.1.3(3)(10)(13). SECTION 601.1. |
| |
| 5. ALL SHEETS DESIGNED BY A DESIGN PROFESSIONAL SHALL |
| BE SIGNED, SEALED AND DATED BY THE DESIGN PROFESSIONAL. |
| SECTION 106.1. SOME SHEETS ARE NOT SIGNED, SEALED OR |
| DATED. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| ONE SET OF THEM LOOSELY ON TOP OF THE |
| COLLATED PLANS TO BE REVIEWED. |