Plan Review Notes
Plan Review Notes For Permit 09060761
Permit Number 09060761
Review Stop E
Sequence Number 1
Notes
Date Text
2009-07-05 12:06:22** DENIED PLANS REVIEW **
  
 1) NOTE: PLANS ARE SUBMITTED ONLY FOR PLAN REVIEW ONLY,
 NO PERMIT APPLICATION HAS BEEN MADE. PLEASE ALSO SEE
 THAT THE PERMIT DESCRIPTION STATED ON THE 2400 N
 FLAGLER DR PROJECT IS THE SAME FOR PHIPPS PARK. IN FACT
 THE CURRIE PARK APPLICATION STATES * OTHER: CURRIE PARK
 RENOVATION*.
  
 IT APPEARS THE DESCRIPTION OF WORK NEEDS TO BE REVISED
 AND LOCATIONS COORDINATED.
  
 EACH APPLICATION DOES NOT NEED TO MENTION THE OTHER
 LOCATIONS. THESE ARE SEPARATE PROJECTS WITH SEPARATE
 PLANS AND APPLICATIONS.
  
 2) NOTE: PLEASE SEE FS 481.219 FOR LANDSCAPE FIRM WHICH
 REQUIRES CERTIFICATE OF AUTHORIZATION NUMBER. SEE FAC
 61G1-16.004, 61G10 FOR REQUIRED TITLE BLOCK
 INFORMATION.
 NO COMPANY PHONE NUMBER.
 NO COMPANY LICENSE NUMBER.
  
 3) NOTE: SOME SHEETS SUBMITTED DO NOT CONTAIN ANY
 SIGNATURE, DATE OR SEAL FROM THE RESPONSIBLE DESIGN
 PROFESSIONAL. SEE EP1.0, A6.0 FOR EXAMPLES.
 481.221, 471.025
  
 4) NOTE: SHEET E-7 STATES 2004 FBC WITH 2007 REVISIONS.
 AS OF MARCH 1ST, 2009 ALL PERMIT APPLICATIONS SHALL BE
 UNDER THE 2007 FBC WITH THE 2009 REVISIONS.
 THIS SAME SHEETS MAKES REFERENCE TO THE 2003 NFPA-101.
 PLEASE SEE FAC 69A-60.004 AS OF DECEMBER 31ST, 2008 THE
 REVISED ADOPTED CODE IS 2006 NFPA-101.
  
 5) NOTE: PLEASE SUBMIT PRESCRIPTIVE LIGHTING
 PERFORMANCE CALCULATIONS FOR NEW RESTROOM BUILDING. SEE
 13-415.AB.5 AND SEE 13-415.AB.2.2 FOR EXTERIOR.
  
 6) NOTE: PLEASE VOLTAGE DROP FOR NEW SUB FEED FROM
 MAIN. SEE FBC 13-413.AB.1
  
 7) NOTE: GROUNDING ELECTRODE CONDUCTOR AND BUILDING
 FOOTER STEEL REQUIRED AT THE DETACHED STRUCTURE.
 250.32,250.50 ETC
  
 8) NOTE: PLEASE KNOW THAT WIND LOAD CALCULATIONS WILL
 BE REQUIRED TO BE SUBMITTED AND REVIEWED FOR MINIMUM
 CODE COMPLIANCE. THIS WILL BE A BUILDING REVIEW COMMENT
 HOWEVER IT IS NOTED FOR INFORMATION ONLY. THIS IS AN
 ITEM WHICH MAY BE A PROVISO ITEM.
 PLEASE ALSO KNOW THAT PER NEW BUILDING OFFICIAL THE
 SITE LIGHTING MAY BE REQUIRED TO BE UNDER A SEPARATE
 PERMIT. PLEASE CONTACT THE NEW CONSTRUCTION SERVICES
 DIRECTOR TO CONFIRM.
  
  
 *** ALL LOW VOLTAGE WORK SHALL BE UNDER SEPARATE
 PERMITS.
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  