2009-07-05 12:06:22 | ** DENIED PLANS REVIEW ** |
| |
| 1) NOTE: PLANS ARE SUBMITTED ONLY FOR PLAN REVIEW ONLY, |
| NO PERMIT APPLICATION HAS BEEN MADE. PLEASE ALSO SEE |
| THAT THE PERMIT DESCRIPTION STATED ON THE 2400 N |
| FLAGLER DR PROJECT IS THE SAME FOR PHIPPS PARK. IN FACT |
| THE CURRIE PARK APPLICATION STATES * OTHER: CURRIE PARK |
| RENOVATION*. |
| |
| IT APPEARS THE DESCRIPTION OF WORK NEEDS TO BE REVISED |
| AND LOCATIONS COORDINATED. |
| |
| EACH APPLICATION DOES NOT NEED TO MENTION THE OTHER |
| LOCATIONS. THESE ARE SEPARATE PROJECTS WITH SEPARATE |
| PLANS AND APPLICATIONS. |
| |
| 2) NOTE: PLEASE SEE FS 481.219 FOR LANDSCAPE FIRM WHICH |
| REQUIRES CERTIFICATE OF AUTHORIZATION NUMBER. SEE FAC |
| 61G1-16.004, 61G10 FOR REQUIRED TITLE BLOCK |
| INFORMATION. |
| NO COMPANY PHONE NUMBER. |
| NO COMPANY LICENSE NUMBER. |
| |
| 3) NOTE: SOME SHEETS SUBMITTED DO NOT CONTAIN ANY |
| SIGNATURE, DATE OR SEAL FROM THE RESPONSIBLE DESIGN |
| PROFESSIONAL. SEE EP1.0, A6.0 FOR EXAMPLES. |
| 481.221, 471.025 |
| |
| 4) NOTE: SHEET E-7 STATES 2004 FBC WITH 2007 REVISIONS. |
| AS OF MARCH 1ST, 2009 ALL PERMIT APPLICATIONS SHALL BE |
| UNDER THE 2007 FBC WITH THE 2009 REVISIONS. |
| THIS SAME SHEETS MAKES REFERENCE TO THE 2003 NFPA-101. |
| PLEASE SEE FAC 69A-60.004 AS OF DECEMBER 31ST, 2008 THE |
| REVISED ADOPTED CODE IS 2006 NFPA-101. |
| |
| 5) NOTE: PLEASE SUBMIT PRESCRIPTIVE LIGHTING |
| PERFORMANCE CALCULATIONS FOR NEW RESTROOM BUILDING. SEE |
| 13-415.AB.5 AND SEE 13-415.AB.2.2 FOR EXTERIOR. |
| |
| 6) NOTE: PLEASE VOLTAGE DROP FOR NEW SUB FEED FROM |
| MAIN. SEE FBC 13-413.AB.1 |
| |
| 7) NOTE: GROUNDING ELECTRODE CONDUCTOR AND BUILDING |
| FOOTER STEEL REQUIRED AT THE DETACHED STRUCTURE. |
| 250.32,250.50 ETC |
| |
| 8) NOTE: PLEASE KNOW THAT WIND LOAD CALCULATIONS WILL |
| BE REQUIRED TO BE SUBMITTED AND REVIEWED FOR MINIMUM |
| CODE COMPLIANCE. THIS WILL BE A BUILDING REVIEW COMMENT |
| HOWEVER IT IS NOTED FOR INFORMATION ONLY. THIS IS AN |
| ITEM WHICH MAY BE A PROVISO ITEM. |
| PLEASE ALSO KNOW THAT PER NEW BUILDING OFFICIAL THE |
| SITE LIGHTING MAY BE REQUIRED TO BE UNDER A SEPARATE |
| PERMIT. PLEASE CONTACT THE NEW CONSTRUCTION SERVICES |
| DIRECTOR TO CONFIRM. |
| |
| |
| *** ALL LOW VOLTAGE WORK SHALL BE UNDER SEPARATE |
| PERMITS. |
| |
| ** IMPORTANT ** |
| ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| INTO TWO SETS/FOLDERS/BINDERS ETC. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| ANY DELAYS. |
| |
| IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| CONTACT THIS REVIEWER. |
| |