2009-07-17 16:56:00 | BUILDING PLAN REVIEW |
| PERMIT: 09060761 |
| ADD: 2400 N FLAGLER DRIVE |
| CONT: "PLAN REVIEW" |
| TEL: (561)644-7446 |
| |
| FL BLD CODE= 2007 FLORIDA BUILDING CODE |
| W/ 2009 FBC SUPPLEMENTS |
| * WEST PALM BEACH AMENDMENTS |
| 1ST REVIEW |
| ACTION: DENIED |
| |
| 1) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER |
| MARCH 1ST, 2009 SHALL BE REVIEWED TO THE 2007 FBC |
| BUILDING WITH 2009 SUPPLEMENTS. |
| |
| 2) PLANS ARE NOT CLEAR AS TO THE NATURE OF WORK. FOR |
| EXAMPLE THE PERMIT APPLICATION INDICATES PICNIC |
| SHELTERS AND TENNIS SHELTERS. |
| SHEET LS-3 INDICATES POLIGON SHELTERS 20'X20' OR |
| 22'X22' |
| SHEET LD-2 INDICATES A 16'-8" X 16'-8" SHELTERS |
| ARE BOTH OF THESE TO BE PICNIC SHELTERS? THERE IS NO |
| DESIGN CRITERIA PROVIDED AT THIS TIME THE PLANS |
| INDICATE "SUBJECT TO ONGOING DESIGN REVIEW. |
| |
| INFORMATIONAL 106.1.1* W.P.B. ADMINISTRATIVE CODE/2004 |
| DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN |
| THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF |
| MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY |
| WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE |
| SPECIFIC TO THE TECHNICAL CODES .CONSTRUCTION DOCUMENTS |
| SHALL BE SUFFICIENT CLARITY TO INDICATE THE LOCATION, |
| NATURE AND EXTENT OF THE WORK PROPOSED AND SHOW IN |
| DETAIL THAT IT WILL CONFORM TO THE PROVISIONS OF THIS |
| CODE AND RELEVANT LAWS, ORDINANCES, RULES AND |
| REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL. |
| |
| 3) THE SAME IS TRUE FOR THE TENNIS SHELTERS FOUND ON |
| SHEET LD-1" SUBJECT TO ONGOING DESIGN REVIEW". |
| INFORMATIONAL 106.1.1* W.P.B. ADMINISTRATIVE CODE/2004 |
| DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN |
| THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF |
| MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY |
| WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE |
| SPECIFIC TO THE TECHNICAL CODES .CONSTRUCTION DOCUMENTS |
| SHALL BE SUFFICIENT CLARITY TO INDICATE THE LOCATION, |
| NATURE AND EXTENT OF THE WORK PROPOSED AND SHOW IN |
| DETAIL THAT IT WILL CONFORM TO THE PROVISIONS OF THIS |
| CODE AND RELEVANT LAWS, ORDINANCES, RULES AND |
| REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL. |
| |
| 4) SHEET E-5 INDICATES THE LIGHT POLES TO BE USED ON |
| THE PROJECT, THE WIND INFORMATION IS PROVIDED FOR 140 |
| MPH BUT THE EXPOSURE IS NOT PROVEDED. THIS LOCATION |
| SHALL BE CONSIDERED A "C" ZONE HAS THAT EXPOSURE FACTOR |
| BEEN INCLUDED INTO THE POLE AND LIGHT FIXTURE DESIGN. |
| ASCE 7-05. |
| |
| 5) SHEET E-6 DOES INDICATE LIGHT POLE FIXTURE TYPES BUT |
| THE EPA FOR FIXTURE TYPE WAS NOT PROVIDED. 106.1.2 |
| ADDITIONAL INFORMATION REQUIRED./ ASCE 7-05. |
| |
| 6) SHEET LS-3 INDICATES THERE TO BE A NAUTICAL |
| PLAYGROND. PLEASE REVIEW THE "GUIDE TO ADA |
| ACCESSIBILITY GUIDELINES FOR PLAY AREAS" FOR ACCESSIBLE |
| ROUTE, PLAY COMPONENTS, GROUND LEVEL AND ELEVATED PLAY |
| COMPONENTS BASED ON TABLE 15.6.2.2. |
| |
| 7) NEW RESTROOM BUILDING: |
| 7A) MISSING WIND DESIGN CRITERIA:2007 FBC 1609.1.1 & |
| CHAPTER 35 REFERENECED STANDARDS RECOGNIZES ASCE 7-05 . |
| ALSO 1603.1.4 WIND DESIGN DATA. |
| 1603.1.4 WIND DESIGN DATA. |
| THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL |
| BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE |
| DESIGN OF THE LATERAL-FORCE-RESISTING SYSTEM OF THE |
| BUILDING: |
| 1. BASIC WIND SPEED (3-SECOND GUST), MILES PER HOUR |
| (KM/HR). |
| |
| 2. WIND IMPORTANCE FACTOR, I W , AND BUILDING |
| CLASSIFICATION FROM TABLE 1604.5 OR TABLE 6-1, ASCE 7 |
| AND BUILDING CLASSIFICATION IN TABLE 1-1, ASCE 7. |
| |
| 3. WIND EXPOSURE, IF MORE THAN ONE WIND EXPOSURE IS |
| UTILIZED, THE WIND EXPOSURE AND APPLICABLE WIND |
| DIRECTION SHALL BE INDICATED. |
| |
| 4. THE APPLICABLE ENCLOSURE CLASSIFICATIONS AND, IF |
| DESIGNING WITH ASCE 7, INTERNAL PRESSURE COEFFICIENT. |
| |
| 5. COMPONENTS AND CLADDING. THE DESIGN WIND PRESSURES |
| IN TERMS OF PSF (KN/M 2 ) TO BE USED FOR THE SELECTION |
| OF EXTERIOR COMPONENTS AND CLADDING MATERIALS NOT |
| SPECIFICALLY |
| DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL. |
| |
| 8) PLEASE PROVIDE ORIGINAL SIGNED AND SEALED SOILS |
| REPORT. 1802.2.1 QUESTIONABLE SOIL. WHERE THE |
| SAFE-SUSTAINING POWER OF THE SOIL IS IN DOUBT, OR WHERE |
| A LOAD-BEARING VALUE SUPERIOR TO THAT SPECIFIED IN THIS |
| CODE IS CLAIMED, THE BUILDING OFFICIAL SHALL REQUIRE |
| THAT THE NECESSARY INVESTIGATION BE MADE. SUCH |
| INVESTIGATION SHALL COMPLY WITH THE PROVISIONS OF |
| SECTIONS 1802.4 THROUGH 1802.6 . |
| |
| 9) SHEET A-1.0 DOES NOT INDICATE COMPLIANCE WITH 1816.1 |
| TERMITE PROTECTION. |
| |
| 10) PLEASE REVIEW 1203.2 WITH THE REQUIREMENT OF 50 % |
| OF REQUIRED VENTILATION IN THE UPPER PORTION OF ROOF. |
| |
| 11)FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING, |
| PROVIDE 2 COPIES OF PRODUCT TESTING REPORTS, MISSING |
| REPORTS ARE AS FOLLOWS: |
| 11A) TRUSS ANCHORS |
| 11B) GLASS BLOCK |
| 11C) LOUVERS |
| 11D) EXTERIOR SWING DOORS |
| 11E) ROOFING ASSEMBLIES |
| |
| 12) WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE |
| PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE |
| REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| |
| 13) ONCE SQ FT AREAS OF PAVILIONS ARE KNOWN STATE RADON |
| FEES WILL BE ASSESSED. |
| |
| JIM WITMER C. B. O. |
| BUILDING PLAN REVIEW II |
| |
| TEL: (561)805-6715 |
| FAX: (561)805-6731 |
| E-MAIL: [email protected] |
| SURVEY: |
| WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES |
| |
| PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| |
| |