2009-07-17 16:56:00BUILDING PLAN REVIEW
 PERMIT: 09060761
 ADD: 2400 N FLAGLER DRIVE
 CONT: "PLAN REVIEW"
 TEL: (561)644-7446
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
 1ST REVIEW
 ACTION: DENIED
  
 1) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER
 MARCH 1ST, 2009 SHALL BE REVIEWED TO THE 2007 FBC
 BUILDING WITH 2009 SUPPLEMENTS.
  
 2) PLANS ARE NOT CLEAR AS TO THE NATURE OF WORK. FOR
 EXAMPLE THE PERMIT APPLICATION INDICATES PICNIC
 SHELTERS AND TENNIS SHELTERS.
 SHEET LS-3 INDICATES POLIGON SHELTERS 20'X20' OR
 22'X22'
 SHEET LD-2 INDICATES A 16'-8" X 16'-8" SHELTERS
 ARE BOTH OF THESE TO BE PICNIC SHELTERS? THERE IS NO
 DESIGN CRITERIA PROVIDED AT THIS TIME THE PLANS
 INDICATE "SUBJECT TO ONGOING DESIGN REVIEW.
  
 INFORMATIONAL 106.1.1* W.P.B. ADMINISTRATIVE CODE/2004
 DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN
 THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY
 WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE
 SPECIFIC TO THE TECHNICAL CODES .CONSTRUCTION DOCUMENTS
 SHALL BE SUFFICIENT CLARITY TO INDICATE THE LOCATION,
 NATURE AND EXTENT OF THE WORK PROPOSED AND SHOW IN
 DETAIL THAT IT WILL CONFORM TO THE PROVISIONS OF THIS
 CODE AND RELEVANT LAWS, ORDINANCES, RULES AND
 REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL.
  
 3) THE SAME IS TRUE FOR THE TENNIS SHELTERS FOUND ON
 SHEET LD-1" SUBJECT TO ONGOING DESIGN REVIEW".
 INFORMATIONAL 106.1.1* W.P.B. ADMINISTRATIVE CODE/2004
 DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN
 THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY
 WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE
 SPECIFIC TO THE TECHNICAL CODES .CONSTRUCTION DOCUMENTS
 SHALL BE SUFFICIENT CLARITY TO INDICATE THE LOCATION,
 NATURE AND EXTENT OF THE WORK PROPOSED AND SHOW IN
 DETAIL THAT IT WILL CONFORM TO THE PROVISIONS OF THIS
 CODE AND RELEVANT LAWS, ORDINANCES, RULES AND
 REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL.
  
 4) SHEET E-5 INDICATES THE LIGHT POLES TO BE USED ON
 THE PROJECT, THE WIND INFORMATION IS PROVIDED FOR 140
 MPH BUT THE EXPOSURE IS NOT PROVEDED. THIS LOCATION
 SHALL BE CONSIDERED A "C" ZONE HAS THAT EXPOSURE FACTOR
 BEEN INCLUDED INTO THE POLE AND LIGHT FIXTURE DESIGN.
 ASCE 7-05.
  
 5) SHEET E-6 DOES INDICATE LIGHT POLE FIXTURE TYPES BUT
 THE EPA FOR FIXTURE TYPE WAS NOT PROVIDED. 106.1.2
 ADDITIONAL INFORMATION REQUIRED./ ASCE 7-05.
  
 6) SHEET LS-3 INDICATES THERE TO BE A NAUTICAL
 PLAYGROND. PLEASE REVIEW THE "GUIDE TO ADA
 ACCESSIBILITY GUIDELINES FOR PLAY AREAS" FOR ACCESSIBLE
 ROUTE, PLAY COMPONENTS, GROUND LEVEL AND ELEVATED PLAY
 COMPONENTS BASED ON TABLE 15.6.2.2.
  
 7) NEW RESTROOM BUILDING:
 7A) MISSING WIND DESIGN CRITERIA:2007 FBC 1609.1.1 &
 CHAPTER 35 REFERENECED STANDARDS RECOGNIZES ASCE 7-05 .
 ALSO 1603.1.4 WIND DESIGN DATA.
 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL-FORCE-RESISTING SYSTEM OF THE
 BUILDING:
 1. BASIC WIND SPEED (3-SECOND GUST), MILES PER HOUR
 (KM/HR).
  
 2. WIND IMPORTANCE FACTOR, I W , AND BUILDING
 CLASSIFICATION FROM TABLE 1604.5 OR TABLE 6-1, ASCE 7
 AND BUILDING CLASSIFICATION IN TABLE 1-1, ASCE 7.
  
 3. WIND EXPOSURE, IF MORE THAN ONE WIND EXPOSURE IS
 UTILIZED, THE WIND EXPOSURE AND APPLICABLE WIND
 DIRECTION SHALL BE INDICATED.
  
 4. THE APPLICABLE ENCLOSURE CLASSIFICATIONS AND, IF
 DESIGNING WITH ASCE 7, INTERNAL PRESSURE COEFFICIENT.
  
 5. COMPONENTS AND CLADDING. THE DESIGN WIND PRESSURES
 IN TERMS OF PSF (KN/M 2 ) TO BE USED FOR THE SELECTION
 OF EXTERIOR COMPONENTS AND CLADDING MATERIALS NOT
 SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL.
  
 8) PLEASE PROVIDE ORIGINAL SIGNED AND SEALED SOILS
 REPORT. 1802.2.1 QUESTIONABLE SOIL. WHERE THE
 SAFE-SUSTAINING POWER OF THE SOIL IS IN DOUBT, OR WHERE
 A LOAD-BEARING VALUE SUPERIOR TO THAT SPECIFIED IN THIS
 CODE IS CLAIMED, THE BUILDING OFFICIAL SHALL REQUIRE
 THAT THE NECESSARY INVESTIGATION BE MADE. SUCH
 INVESTIGATION SHALL COMPLY WITH THE PROVISIONS OF
 SECTIONS 1802.4 THROUGH 1802.6 .
  
 9) SHEET A-1.0 DOES NOT INDICATE COMPLIANCE WITH 1816.1
 TERMITE PROTECTION.
  
 10) PLEASE REVIEW 1203.2 WITH THE REQUIREMENT OF 50 %
 OF REQUIRED VENTILATION IN THE UPPER PORTION OF ROOF.
  
 11)FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING,
 PROVIDE 2 COPIES OF PRODUCT TESTING REPORTS, MISSING
 REPORTS ARE AS FOLLOWS:
 11A) TRUSS ANCHORS
 11B) GLASS BLOCK
 11C) LOUVERS
 11D) EXTERIOR SWING DOORS
 11E) ROOFING ASSEMBLIES
  
 12) WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 13) ONCE SQ FT AREAS OF PAVILIONS ARE KNOWN STATE RADON
 FEES WILL BE ASSESSED.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
 SURVEY:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
  