Text |
2009-11-30 14:28:10 | DENIED |
| REFERENCE: |
| FBC-2007 PLUMBING |
| |
| 1. SHT E-2 LOAD CALCULATIONS INDICATE 4 FRYERS, HOT DOG |
| & NACHO MACHINES ETC. PER SECTION 1003.1 AN INTERCEPTOR |
| & SEPARATOR MAY BE REQUIRED. PER SECTION 1003.3.1 A |
| GREASE INTERCEPTOR OR AUTOMATIC GREASE REMOVAL DEVISE |
| SHALL BE REQUIRED TO RECEIVE THE DRAINAGE FROM FIXTURES |
| AND EQUIPMENT WITH GREASE-LADEN WASTE LOCATED IN FOOD |
| PREPARATION AREAS , SUCH AS IN RESTAURANTS, HOTEL |
| KITCHENS, HOSPITALS, BARS, FACTORY CAFETERIAS AND |
| CLUBS. FIXTURES AND EQUIPMENT SHALL INCLUDE POT SINKS, |
| PRERINSE SINKS; SOUP KETTLES OR SIMILAR DEVICES; WOK |
| STATIONS; FLOOR DRAINS OR SINKS INTO WHICH KETTLES ARE |
| DRAINED; AUTOMATIC HOOD WASH UNITS AND DISHWASHERS WITH |
| PRERINSE SINKS. PLEASE SEE TABLES 1003.3.4.1 & |
| 1003.3.5.1. INFORMATION REQUIRED FOR EACH TABLE SHALL |
| BE SUBMITTED TO DETERMINE THE REQUIRED |
| INTERCEPTOR/GREASE REMOVAL DEVISE SIZE. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| ONE SET OF THEM LOOSELY ON TOP OF THE |
| COLLATED PLANS TO BE REVIEWED. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |