2009-07-10 09:00:10DENIED
 REFERENCE:
 FBC-2007 RESIDENTIAL
  
 1. SHT 2 OF 6 THE SANITARY ISOMETRIC RISER DIAGRAM DOES
 NOT REFLECT THE FLOOR PLAN, NOR DOES IT MEET CODE
 REQUIREMENTS. THE RISER DIAGRAM SHOWS THE LAVS PAST THE
 TUBS, BUT THE FLOOR PLAN SHOWS THE LAVS AHEAD OF THE
 WATER CLOSETS. -- ALSO THE FIXTURES FROM THE SECOND
 FLOOR SHALL NOT DRAIN THROUGH THE VENT FOR THE FIRST
 FLOOR FIXTURES. SECTIONS 3107.1, 3107.2 & 3107.3. --
 THE SECOND FLOOR FIXTURES SHALL NOT DISCHARGE THROUGH
 THE HORIZONTAL WET VENT FOR THE FIRST FLOOR BATHROOM
 FIXTURES. SECTION 3108.1. -- A SECOND RISER CONNECTED
 PRIOR TO THE BATHROOM FIXTURES IS REQUIRED FOR THE
 SECOND FLOOR BATHROOM FIXTURES.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  