Date |
Text |
2009-07-10 09:00:10 | DENIED |
| REFERENCE: |
| FBC-2007 RESIDENTIAL |
| |
| 1. SHT 2 OF 6 THE SANITARY ISOMETRIC RISER DIAGRAM DOES |
| NOT REFLECT THE FLOOR PLAN, NOR DOES IT MEET CODE |
| REQUIREMENTS. THE RISER DIAGRAM SHOWS THE LAVS PAST THE |
| TUBS, BUT THE FLOOR PLAN SHOWS THE LAVS AHEAD OF THE |
| WATER CLOSETS. -- ALSO THE FIXTURES FROM THE SECOND |
| FLOOR SHALL NOT DRAIN THROUGH THE VENT FOR THE FIRST |
| FLOOR FIXTURES. SECTIONS 3107.1, 3107.2 & 3107.3. -- |
| THE SECOND FLOOR FIXTURES SHALL NOT DISCHARGE THROUGH |
| THE HORIZONTAL WET VENT FOR THE FIRST FLOOR BATHROOM |
| FIXTURES. SECTION 3108.1. -- A SECOND RISER CONNECTED |
| PRIOR TO THE BATHROOM FIXTURES IS REQUIRED FOR THE |
| SECOND FLOOR BATHROOM FIXTURES. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| ONE SET OF THEM LOOSELY ON TOP OF THE |
| COLLATED PLANS TO BE REVIEWED. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |