Plan Review Notes
Plan Review Notes For Permit 09060742
Permit Number 09060742
Review Stop M
Sequence Number 1
Notes
Date Text
2009-07-17 16:09:24REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PAGE A6 SHOWS CONDENSER AT REAR OF HOUSE WHILE M1
 SHOWS CONDENSERS ON SIDE OF HOUSE. PLEASE CORRELATE
 PLANS AND SHOW THE CORRECT LOCATION ON SITE PLAN FOR
 ZONING REVIEW.
  
 2. THE ENERGY CODE COMPLIANCE FORM SUBMITTED IS NO
 LONGER VALID. THE CORRECT FORM FOR THIS PROJECT IS FORM
 1100A-08 AS OF MARCH 1, 2009. PLEASE SUBMIT THE CORRECT
 COMPLETED FORM TO DEMONSTRATE COMPLIANCE WITH FBC-R
 CHAPTER 11
  
 3. PROVIDE COOLING AND HEATING LOAD CALCULATIONS
 ATTACHED TO THE ENERGY CODE COMPLIANCE FORM IN
 ACCORDANCE WITH FBC-R SECTION N1107.AB.1
  
 4. PROVIDE EQUIPMENT SCHEDULE ON PLANS PER FBC-R
 SECTION M1401.1
  
 5. DUCT SIZE MISSING ON PLANS FROM AHU TO FIRST
 DISTRIBUTION BOX. PROVIDE MISSING INFORMATION PER FBC-R
 SECTION N1110.A.1
  
 6. CONTRACTOR SHALL PROVIDE SIGNATURE AND LICENSE
 NUMBER ON PLANS AS DESIGNER OF RECORD.
  
 7. PROVIDE MANUAL D TO SHOW JUSTIFICATION FOR DUCT
 DESIGN PER FBC-R SECTION N1110.AB.1.
  