Plan Review Notes
Plan Review Notes For Permit 09060742
Permit Number 09060742
Review Stop B
Sequence Number 1
Notes
Date Text
2009-07-21 14:11:522007 FBC W/2009 REVISIONS
 RESIDENTIAL ADDITION
  
 DENIED BY BUILDING
  
 1) SUBMIT TWO COPIES OF A SIGNED AND SEALED SITE PLAN
 OR A SURVEY SHOWING THE LOCATION OF THE PROPOSED
 ADDITION AND DISTANCES TO THE PROPERTY LINES.
  
 2) SHEET 1 OF THE PLANS SPECIFIES THE SCOPE OF WORK AS
 A LEVEL 2 ALTERATION. THIS IS INCORRECT. THE PROJECT IS
 A LEVEL 3 ALTERATION AND AN ADDITION.
  
 3) THE VALUE SPECIFIED FOR THE PROJECT ON THE
 APPLICATION IS LOW AND HAS BEEN ADJUSTED BASED ON ICC
 VALUATION TABLES. ADDITIONAL PERMIT FEES ARE OWED.
  
 4) THE WINDOW BUCK DETAIL ON SHEET 5 DOES NOT SPECIFY
 THE FASTENERS OR SPACING FOR ATTACHING THE BUCKS TO THE
 MASONRY OPENINGS. PLEASE SPECIFY ATTACHMENT.
  
 5) THE DOOR BUCK DETAIL ON SHEET 5 DOES NOT INDICATE
 THE ATTACHMENT OF THE BUCK TO THE MASONRY OPENING.
 PLEASE SPECIFY THE ATTACHMENTS. ALSO THE DOOR JAMB TO
 BUCK ATTACHMENT IS SPECIFIED WITH 8D NAILS AND THE
 PRODUCT APPROVAL SPECIFIES SCREWS. PLEASE CORRECT.
  
 6) SPECIFY THE REQUIRED LOADS FOR THE FLOOR TRUSSES ON
 THE PLANS. FBC R 301.4 AND R301.5.
  
 7) FBC R803.2.3.1 REQUIRES THE ROOF SHEATHING TO BE
 FASTENED WITH 8D RING-SHANK NAILS. PLEASE REVISE THE
 NOTES ON THE WALL SECTION ON SHEET 5 OF THE PLANS.
  
 8) SPECIFY THE INSULATION ON THE WALL SECTION AT THE
 MASONRY WALL AND AT THE EXTERIOR WALL AT THE FLOOR
 TRUSSES. FBC 13-600
  
 9) THE ROOF LOADS SPECIFIED ON SHEET 1 DO NOT MATCH THE
 ONES ON THE TRUSS DRAWINGS. PLEASE CORRECT.
  
 10) WHERE STUCCO IS TO BE APPLIED TO LATH OVER FRAME
 CONSTRUCTION A BOND BREAK IS REQUIRED BETWEEN THE
 WATER-RESISTIVE BARRIER AND THE STUCCO PER FBC
 R703.6.3. SPECIFY TWO LAYERS OF APPROVED
 WATER-RESISTANT BARRIER (ASPHALT FELT) OR OTHER
 APPROVED METHOD OR MATERIALS.
  
 11) THE PRODUCT APPROVALS THAT WERE SUBMITTED FOR THE
 GAF SHINGLES FL183 IS FOR THE 2001 FBC AND IS NOT
 ACCEPTABLE FOR THE CURRENT CODE WHICH IS THE 2007 FBC.
 ALSO THE NOA # 06-0331.12 FOR THE SHINGLES IS CLOSED.
 SUBMIT TWO COPIES OF CURRENT PRODUCT APPROVALS FOR THE
 ASPHALT ROOF SHINGLES. DCA RULE 9B-72
  
 12) THE FL PRODUCT APPROVAL COVERSHEET FOR THE SINGLE
 HUNG WINDOWS IS FOR THE 2004 FBC AND IS NOT ACCEPTABLE
 FOR THE CURRENT CODE WHICH IS THE 2007 FBC. HOWEVER,
 THE MIAMI DADE NOA THAT WAS SUBMITTED IS CURRENT AND
 ACCEPTABLE WITHOUT THE FL COVERSHEET.
  
 13) THE TRUSS LAYOUT AND DRAWINGS ARE NOT REQUIRED TO
 BE SUBMITTED FOR PLAN REVIEW FOR SINGLE FAMILY
 RESIDENCES. HOWEVER, THEY ARE REQUIRED TO BE GIVEN TO
 THE BUILDING INSPECTOR AT THE ROOF FRAMING INSPECTION.
 BECAUSE THE TRUSS INFORMATION WAS SUBMITTED IT WAS
 REVIEWED AND A NUMBER OF DEFICIENCIES WERE FOUND AS
 FOLLOWS. THE TRUSS LAYOUT AND DRAWINGS ARE REQUIRED TO
 HAVE THE ORIGINAL SIGNATURE OF THE TRUSS ENGINEER PER
 FS471. SIGNATURE STAMPS AND COPIES ARE NOT ACCEPTABLE.
 THE ROOF LOADS DO NOT CORRESPOND TO THE PLANS. THE
 BOTTOM CORD LIVE LOAD FOR THE ROOF TRUSSES IS REQUIRED
 TO BE A MINIMUM OF 10 PSF PER FBC R301.5. THE LOADS ARE
 NOT SPECIFIED ON THE TRUSS LAYOUT. THE TRUSS DRAWINGS
 ARE MISSING REQUIRED INFORMATION SUCH AS UPLIFT,
 WINDSPEED, DESIGN CRITERIA, ETC. PAGE 8 OF THE TRUSS
 DRAWINGS SPECIFIES THE WRONG EDITION OF ASCE 7, WHICH
 SHOULD BE ASCE 7-05 FOR THE 2007 FBC. PAGE 1 LISTS THE
 TRUSS DESIGN PER IBC NOT FBC. PLEASE CORRECT THE
 DEFICIENCIES BEFORE TRUSS DRAWINGS ARE GIVEN TO THE
 BUILDING INSPECTOR AT THE ROOF FRAMING INSPECTION.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]