Plan Review Notes
Plan Review Notes For Permit 09060714
Permit Number 09060714
Review Stop E
Sequence Number 1
Notes
Date Text
2009-07-03 10:46:01 
 ** DENIED
  
  
 1) NOTE: NEED LAYOUT OF EQUIPMENT LOCATIONS IN ROOMS
 AND AREAS. SEE NOTE #3.
  
 2) NOTE: PLEASE INDICATE CONDUCTOR SIZES FOR EQUIPMENT.
 IS PUMP 120V? EXISTING? NEW? THE PERMIT WHICH WAS
 PULLED IN OCTOBER DID NOT PROVIDE ELECTRICAL
 INFORMATION OR VALUE FOR COMPLETE SCOPE.
 310.16, FBC 106.1.1, 106.1.2
  
 3) NOTE: PLANS NEED TO SHOW LOCATIONS AND ALL WIRING
 METHODS UNDER NEC 500, 500.4,.6,501.5, 505.
 PLEASE SEE NFPA-50A, AND B.
  
 4) NOTE: PERSON RESPONSIBLE FOR PLANS NEEDS TO PRINT
 NAME AND SIGN WHEN MEETING EXCEPTIONS TO FS
 471.003,481.229.
  
 5) NOTE: VALUE FOR COMPLETE SCOPE OF WORK INCLUDING ALL
 EQUIPMENT EVEN IF OWNER SUPPLIED NEEDS TO BE INCLUDED.
 FBC 108.3. AS THE COMPLETED VALUE AND SCOPE WAS NOT
 PART OF MAIN PERMIT, IT LEAVES ALL PUMP AND WIRING ETC
 VALUE UNDER ELECTRICAL. THE PERMIT MAY ALSO NEED ONE
 FOR ANY LINE VOLTAGE EQUIPMENT AS LOW VOLTAGE PERMIT
 WAS APPLIED. FBC 105.1 IT IS NOT KNOWN AT THIS TIME.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  