2009-07-27 09:49:25 | |
| ** DENIED REVIEW. ** |
| |
| 1) NOTE: THE SEAL USED BY THE ENGINEER ON PLANS IS NO |
| LONGER VALID IN THE STATE OF FLORIDA. IN FACT THE SEAL |
| HAS NOT BEEN VALID FOR MANY YEARS. THE RULING UNDER |
| FLORIDA ADMINISTRATIVE CODE 61G15-23.001 REQUIRED |
| ENGINEERS TO UPDATE THEIR SEALS TO NEW REQUIREMENTS. |
| THIS RULE WAS PASSED IN FEBRUARY OF 2004. THE STATE DID |
| GRANT AN EXTENSION HOWEVER THE FINAL DATE OF EXTENSION |
| WAS DECEMBER 31ST 2005. AT THAT TIME THE SEALS WITH THE |
| WORDING OF *CERTIFICATE* WERE NO LONGER ACCEPTABLE OR |
| TO BE USED. |
| THE LICENSE NUMBER ON SAID PLANS IS STILL VALID WITH |
| THE DEPARTMENT OF BUSINESS AND PROFESSIONAL REGULATION. |
| PLEASE OBTAIN NEW SEAL. PLEASE SIGN, DATE AND SEAL NEW |
| PLANS UNDER FLORIDA STATUTES 471.025. |
| |
| ** THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY |
| OTHER TRADES. |
| |
| 2) NOTE: PLEASE SEE THAT THE ELECTRICAL DETAIL/PLAN |
| SUBMITTED CONTAINS NO DESIGN PROFESSIONAL PER 471, 481 |
| OR 489. WHEN MEETING EXCEPTIONS TO 471.003 THEN PLANS |
| MUST STILL BE UNDER THE DESIGN OF A LICENSED CONTRACTOR |
| PER 489. |
| |
| 3) NOTE: THE APPLIED VALUE FOR THE COMPLETE SCOPE OF |
| WORK SHALL INCLUDE ALL LABOR, MATERIALS, EQUIPMENT, |
| DESIGN COST, INSTALLATION ETC EVEN IF ANY OF THESE |
| ITEMS ARE OWNER SUPPLIED. THE APPLIED VALUE FOR THE |
| COMPLETE SCOPE OF WORK AT $7,000 IS LOW. |
| FBC 108.3. |
| PLEASE PROVIDE COPY OF SIGNED CONTRACTS FOR ALL OF THE |
| ABOVE. |
| |
| ** PER BUILDING OFFICIAL. PLANS AND PERMIT APPLICATIONS |
| ARE NO LONGER RELEASED AND SHALL REMAIN ON FILE. |
| |
| |
| |
| |
| IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| CONTACT THIS REVIEWER. |
| |