2009-06-26 09:08:35RE-ROOF BUILDING REVIEW CHECKLIST.
 REVIEW UNDER 2007 FBC WITH 2009 REVISIONS.
  
 1- PROVIDE RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13
 FLORIDA STATUTE.
 NOTE: THIS MAY BE RECORDED AT TIME OF PERMIT PICK UP.
  
 2- CLEARLY MARK ON NOA 06-0601.08 SUBMITTED SPECIFIC
 APPROVED FLAT ROOF ASSEMBLY WITH SPECIFIC MAXIMUM
 DESIGN PRESSURES TO BE INSTALLED TO VERIFY COMPLIANCE
 WITH THE DESIGN PRESSURES OF SEC. 1609 OF 2007 FBC.
 IF THE SELECTED ASSEMBLY DOESN'T MEET THE DESIGN
 PRESSURES FOR THIS BUILDING AND THE ASSEMBLY IS LIMITED
 BY GENERAL LIMITATION #7, THEN NEED TO PROVIDE SIGNED
 AND SEALED RAS 117 CALCULATIONS. ON THE OTHER HAND, IF
 SELECTED ASSEMBLY IS LIMITED BY GENERAL LIMITATION #9
 AND IT DOESN'T MEET THE DESIGN PRESSURES OF THIS
 BUILDING, THEN THE ASSEMBLY CAN'T BE USED IN THIS
 BUILDING. SEE GENERAL LIMITATION #7 AND #9 ON LAST PAGE
 OF NOA SUBMITTED.
  
 ***NOTE: ACCORDING TO 2009 REVISIONS TO THE 2007 FBC
 THIS BUILDING IS LOCATED ON EXPOSURE "C". TAKE THIS
 INTO CONSIDERATION WHEN CALCULATING THE DESIGN
 PRESSURES FOR THIS BUILDING.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER