2009-08-17 18:16:04 | THE COMMENTS FROM THE PREVIOUS PLAN REVIEW (7/6/09) |
| HAVE NOT BEEN ADDRESSED. THE SAME COMMENTS HAVE BEEN |
| REPEATED HERE AGAIN: |
| |
| BUILDING PLAN REVIEW |
| *******DENIED******* |
| ROBERT BROWN (561) 805 6652 |
| E-MAIL: [email protected] |
| |
| FBC = FLORIDA BUILDING CODE 2007 |
| FBC*= FLORIDA BUILD'G CODE (CITY AMEND) |
| F.S.= FLORIDA (STATE) STATUTE |
| |
| THE COMMENTS FROM THE PREVIOUS PLAN REVIEW (7/6/09) |
| WERE NOT BEEN ADDRESSED. THE SAME COMMENTS HAVE BEEN |
| REPEATED HERE AGAIN: |
| |
| 1) FBC 1604.2 ANCHOR BOLTS FOR 25'-0" LIGHT POLE WITH |
| FIXTURE F3. PLAN SHEET E05, DETAIL 4, SPECIFIES 4 |
| ANCHOR BOLTS 3/4" DIA. X 32" WHICH IS NOT CORRECT. THE |
| BOLTS SHOULD BE 4 ANCHOR BOLTS 1" DIA. X 36" AS |
| SPECIFIED ON THE SUBMITTED AMERON POLE PRODUCTS |
| DIVISION DRAWING NO. 0905-043 (8.5" X 11" DRAWING |
| SHEET). AMEND PLAN SHEET E05. |
| |
| 2) FBC 1604.2 BOLT CIRCLE DIAMETER FOR ANCHOR BOLTS FOR |
| 25'-0" LIGHT POLE WITH FIXTURE F3. PLAN SHEET E05, |
| DETAIL 4, DOES NOT SPECIFY THE BOLT CIRCLE DIAMETER FOR |
| THE 4 ANCHOR BOLTS. THE BOLT CIRCLE DIAMETER SHOULD BE |
| 11.5" AS SPECIFIED ON THE SUBMITTED AMERON POLE |
| PRODUCTS DIVISION DRAWING NO. 0905-043 (8.5" X 11" |
| DRAWING SHEET). AMEND PLAN SHEET E05. |
| |
| **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| |
| END OF REVIEW COMMENTS |
| THE CODE REFERENCES GIVE ADDITIONAL INFO |
| TELEPHONE: (561) 805 6652 ROBERT BROWN |