Plan Review Notes
Plan Review Notes For Permit 09060657
Permit Number 09060657
Review Stop E
Sequence Number 1
Notes
Date Text
2009-07-03 15:48:43 
 ** DENIED
  
 ** BASED ON THE COMMENTS BELOW. IF A PERMIT ONLY FOR
 UNDERGROUND CONDUIT INSTALLATIONS WOULD ALLEVIATE ANY
 DELAYS IN THE PROJECT START DATE THIS MAY BE DONE UNDER
 SEPARATE PERMIT APPLICATION(S).
 GAVE INFORMATION TO CONTRACTOR AS THIS MAY BE AN OPTION
 TO GET STARTED.
  
  
 1) NOTE: TWO PERMIT APPLICATIONS WERE SUBMITTED FOR
 09060658 AND 09060657. BOTH FOR THE SAME LOCATION
 ADDRESS OF * @151 S FLAGLER*. PER THE PLANS THERE ARE
 TWO SERVICE POINTS WHICH NEED TO CONTAIN SEPARATE
 ADDRESSES.
 AN E-MAIL WAS SENT TO ADDRESSING REVIEWER TO
 ADJUSTMENTS. PLEASE BE SURE ADDRESS IS NOTED ON PLANS.
 FOR ANY SHEETS WHICH DO NOT NEED TO BE REVISED FOR CODE
 COMMENTS MAY HAVE NEW ADDRESS PLACED NEATLY ON TITLE
 BLOCKS.
 FAC 61G15-23.002, FBC 106.5 FOR RECORD DOCUMENTS.
  
 2) NOTE: PLEASE SEE RISER. THERE IS AN EQUIPMENT
 GROUNDING CONDUCTOR SHOWN FROM FPL METER TO THE FIRST
 MEANS OF DISCONNECT. AS THE NEC REQUIRES THE FIRST
 MEANS OF DISCONNECT TO BE BONDED IF AN EQUIPMENT
 GROUNDING CONDUCTOR IS INSTALLED THIS WOULD CREATE A
 PARALLEL PATH WITH THE GROUNDED/NEUTRAL CONDUCTOR. THIS
 COULD CREATE OBJECTIONABLE CURRENT WHICH IS NOT
 PERMITTED.
 PLEASE SEE 250.24, 250.6.
  
 3) NOTE: THE RISER INDICATES TAPS FROM THE SECONDARY
 SIDE OF THE TRANSFORMER GOING INTO A GUTTER THEN BEING
 TAPPED AGAIN TO GO TO EACH OF THE PANELS. THIS WOULD BE
 TAPPING A TAP CONDUCTOR WHICH IS NOT PERMITTED.
 EACH SET OF TAPPED CONDUCTORS MAY GO TO EACH PANEL
 HENCE EACH TERMINATING IN OVER CURRENT PROTECTION AS
 REQUIRED.
 240.21,310.16,240.4
  
 4) NOTE: RISER ONLY INDICATES ONE GROUND ROD. PLEASE
 SEE 250.56. PLEASE EXPLAIN HOW THE REQUIRED RESISTANCE
 WILL BE OBTAINED IN SPECIFIC SOIL CONDITIONS BASED ONLY
 ON THE ONE 10FT GROUND ROD.
  
 5) NOTE: SPOKE TO CONTRACTOR. WIND LOAD CALCULATIONS
 ARE TO BE SUBMITTED. PLEASE BE SURE CALCULATIONS
 COORDINATE WITH BOTH TYPE OF POLE SUBMITTED AND SHOWN
 ON PLANS.
  
 6) NOTE: PLEASE KNOW THAT PART OF A PROVISO WHICH MAY
 BE SET UP IS FOR THE PANEL SCHEDULE TO BE SPECIFIC TO
 LOCATIONS. STATING *RECEPTACLES*, UPPER/LOWER ETC IS
 NOT SPECIFIC. ALPHA/NUMERICAL DESIGNATIONS MAY USED AT
 LATER DATE.
 408.4
  
 7) NOTE: PLEASE VERIFY THE RISER WHICH INDICATE 4
 PANELS YET ONLY THREE PANEL SCHEDULES WERE SUBMITTED
 AND SHOWN. 215.5,408.4, 240.4, 240.21, 310.16.
 CAN NOT VERIFY CODE COMPLIANCE IF THERE IS GOING TO BE
 ANOTHER PANEL.
  
 8) NOTE: PLEASE CLARIFY THE AIC RATING OF EACH PANEL.
 STATES 10K, HOWEVER IS THIS FOR MAIN, BRANCH BREAKERS
 OR BOTH?
  
 9) NOTE: SERVICE EQUIPMENT SHALL BE ABOVE THE BASE
 FLOOD ELEVATION. PLEASE OBTAIN THE BFE BASED ON FEMA
 CHARTS. THIS IS FLOOD ZONE A.
  
 10) NOTE: RISER SHOWS A 2-POLE SINGLE PHASE
 INSTALLATION TO THE TRANSFORMER AND THE SAME TO THE
 PANELS. ( GUTTER AS SHOWN). PLEASE EXPLAIN THE
 GROUNDED/NEUTRAL CONDUCTORS BEING INSTALLED FROM THE
 MAIN TO THE TRANSFORMER IF THIS IS A SEPARATELY DERIVED
 SYSTEM?
 250.20,250.30,250.50,250.66 ETC
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  