Plan Review Notes For Permit 09060657 |
Permit Number |
09060657 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2009-07-06 19:23:37 | BUILDING PLAN REVIEW | | *******DENIED******* | | ROBERT BROWN (561) 805 6652 | | E-MAIL: [email protected] | | | | FBC = FLORIDA BUILDING CODE 2007 | | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) | | F.S.= FLORIDA (STATE) STATUTE | | | | 1) FBC 1604.2 ANCHOR BOLTS FOR 25'-0" LIGHT POLE WITH | | FIXTURE F3. PLAN SHEET E05, DETAIL 4, SPECIFIES 4 | | ANCHOR BOLTS 3/4" DIA. X 32" WHICH IS NOT CORRECT. THE | | BOLTS SHOULD BE 4 ANCHOR BOLTS 1" DIA. X 36" AS | | SPECIFIED ON THE SUBMITTED AMERON POLE PRODUCTS | | DIVISION DRAWING NO. 0905-043 (8.5" X 11" DRAWING | | SHEET). AMEND PLAN SHEET E05. | | | | 2) FBC 1604.2 BOLT CIRCLE DIAMETER FOR ANCHOR BOLTS FOR | | 25'-0" LIGHT POLE WITH FIXTURE F3. PLAN SHEET E05, | | DETAIL 4, DOES NOT SPECIFY THE BOLT CIRCLE DIAMETER FOR | | THE 4 ANCHOR BOLTS. THE BOLT CIRCLE DIAMETER SHOULD BE | | 11.5" AS SPECIFIED ON THE SUBMITTED AMERON POLE | | PRODUCTS DIVISION DRAWING NO. 0905-043 (8.5" X 11" | | DRAWING SHEET). AMEND PLAN SHEET E05. | | | | **QUOTE PERMIT# ON ALL CORRESPONDENCE** | | | | END OF REVIEW COMMENTS | | THE CODE REFERENCES GIVE ADDITIONAL INFO | | TELEPHONE: (561) 805 6652 ROBERT BROWN | | E-MAIL: [email protected] |
|