Plan Review Notes
Plan Review Notes For Permit 09060657
Permit Number 09060657
Review Stop B
Sequence Number 1
Notes
Date Text
2009-07-06 19:23:37BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN (561) 805 6652
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2007
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
 F.S.= FLORIDA (STATE) STATUTE
  
 1) FBC 1604.2 ANCHOR BOLTS FOR 25'-0" LIGHT POLE WITH
 FIXTURE F3. PLAN SHEET E05, DETAIL 4, SPECIFIES 4
 ANCHOR BOLTS 3/4" DIA. X 32" WHICH IS NOT CORRECT. THE
 BOLTS SHOULD BE 4 ANCHOR BOLTS 1" DIA. X 36" AS
 SPECIFIED ON THE SUBMITTED AMERON POLE PRODUCTS
 DIVISION DRAWING NO. 0905-043 (8.5" X 11" DRAWING
 SHEET). AMEND PLAN SHEET E05.
  
 2) FBC 1604.2 BOLT CIRCLE DIAMETER FOR ANCHOR BOLTS FOR
 25'-0" LIGHT POLE WITH FIXTURE F3. PLAN SHEET E05,
 DETAIL 4, DOES NOT SPECIFY THE BOLT CIRCLE DIAMETER FOR
 THE 4 ANCHOR BOLTS. THE BOLT CIRCLE DIAMETER SHOULD BE
 11.5" AS SPECIFIED ON THE SUBMITTED AMERON POLE
 PRODUCTS DIVISION DRAWING NO. 0905-043 (8.5" X 11"
 DRAWING SHEET). AMEND PLAN SHEET E05.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6652 ROBERT BROWN
 E-MAIL: [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved