Plan Review Notes For Permit 09060605 |
Permit Number |
09060605 |
|
Review Stop |
FIRE |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2009-09-01 21:19:39 | *****DENIED***** | | | | OLD COMMENTS FROM PREVIOUS REVIEW WHICH STILL NEED TO | | BE ADDRESSED: | | | | | | 2. ON SHEET 1 (OF 17) IN THE SEQUENCE OF OPERATIONS | | MATRIX, AMEND TO REFLECT THAT SMOKE DUCT DETECTORS | | SHALL INITIATE A GENERAL FIRE (AS PER LOCAL CODE) . | | SEQUENCE OF OPERATIONS MATRIX STILL INDICATES A | | SUPERVISORY SIGNAL FOR DUCT SMOKE DETECTOR | | | | 5. CORRELATE DRAWING MATCHLINES ACCORDINGLY. FOR | | EXAMPLE, SHEET 2 (OF 17)' S MATCHLINE IS NOTED AS | | "CONTINUED ON SHEET FA-2.5" , HOWEVER THERE IS NO | | FA-2.5 SHEET IN THE DRAWING LIST AND/OR THE PLAN SET. | | | | NEW COMMENT | | | | A. EXPLAIN WHY CERTAIN DEVICES SHOWN ON SHEET 9 (I.E. | | SMOKE DETECTORS - ABOVE THE FACP, IN THE SPRINKLER PUMP | | ROOM) ARE NOT SHOWN ON SHEET 2 . | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|