Plan Review Notes
Plan Review Notes For Permit 09060605
Permit Number 09060605
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2009-09-01 21:19:39*****DENIED*****
  
 OLD COMMENTS FROM PREVIOUS REVIEW WHICH STILL NEED TO
 BE ADDRESSED:
  
  
 2. ON SHEET 1 (OF 17) IN THE SEQUENCE OF OPERATIONS
 MATRIX, AMEND TO REFLECT THAT SMOKE DUCT DETECTORS
 SHALL INITIATE A GENERAL FIRE (AS PER LOCAL CODE) .
 SEQUENCE OF OPERATIONS MATRIX STILL INDICATES A
 SUPERVISORY SIGNAL FOR DUCT SMOKE DETECTOR
  
 5. CORRELATE DRAWING MATCHLINES ACCORDINGLY. FOR
 EXAMPLE, SHEET 2 (OF 17)' S MATCHLINE IS NOTED AS
 "CONTINUED ON SHEET FA-2.5" , HOWEVER THERE IS NO
 FA-2.5 SHEET IN THE DRAWING LIST AND/OR THE PLAN SET.
  
 NEW COMMENT
  
 A. EXPLAIN WHY CERTAIN DEVICES SHOWN ON SHEET 9 (I.E.
 SMOKE DETECTORS - ABOVE THE FACP, IN THE SPRINKLER PUMP
 ROOM) ARE NOT SHOWN ON SHEET 2 .
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722