Plan Review Notes For Permit 09060605 |
Permit Number |
09060605 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2009-07-24 13:32:15 | *****DENIED***** | | | | 1. ON SHEET 1 (OF 17), THE FIRE ALARM DRAWING LIST'S | | DRAWING NUMBERS DO NOT CORRELATE WITH THOSE LISTED IN | | THE TITLE BLOCKS OF THE SUBMITTED PLAN SHEETS. AMEND | | DRAWING NUMBER IN THE DRAWING LEGEND TO CORRELATE WITH | | THAT LISTED IN THE TITLE BLOCK. | | | | 2. ON SHEET 1 (OF 17) IN THE SEQUENCE OF OPERATIONS | | MATRIX, AMEND TO REFLECT THAT SMOKE DUCT DETECTORS | | SHALL INITIATE A GENERAL FIRE (AS PER LOCAL CODE) . | | | | 3. PROVIDE INFORMATION/SPECIFICATIONS FOR THE VESDA | | FIRE ALARM SYSTEM. | | | | 4. FIRE ALARM DEVICES ARE SHOWN FOR THE FUTURE PHASES | | OF THE FIRST LEVEL FIRE ALARM PLAN, HOWEVER NO SUCH | | DEVICES ARE SHOWN FOR THE FUTURE SPACES ON THE SECOND | | THRU FIFTH LEVEL. PLEASE EXPLAIN | | | | 5. IN REFERENCE TO COMMENT #1, CORRELATE DRAWING | | MATCHLINES ACCORDINGLY. | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|