Plan Review Notes
Plan Review Notes For Permit 09060605
Permit Number 09060605
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2009-07-24 13:32:15*****DENIED*****
  
 1. ON SHEET 1 (OF 17), THE FIRE ALARM DRAWING LIST'S
 DRAWING NUMBERS DO NOT CORRELATE WITH THOSE LISTED IN
 THE TITLE BLOCKS OF THE SUBMITTED PLAN SHEETS. AMEND
 DRAWING NUMBER IN THE DRAWING LEGEND TO CORRELATE WITH
 THAT LISTED IN THE TITLE BLOCK.
  
 2. ON SHEET 1 (OF 17) IN THE SEQUENCE OF OPERATIONS
 MATRIX, AMEND TO REFLECT THAT SMOKE DUCT DETECTORS
 SHALL INITIATE A GENERAL FIRE (AS PER LOCAL CODE) .
  
 3. PROVIDE INFORMATION/SPECIFICATIONS FOR THE VESDA
 FIRE ALARM SYSTEM.
  
 4. FIRE ALARM DEVICES ARE SHOWN FOR THE FUTURE PHASES
 OF THE FIRST LEVEL FIRE ALARM PLAN, HOWEVER NO SUCH
 DEVICES ARE SHOWN FOR THE FUTURE SPACES ON THE SECOND
 THRU FIFTH LEVEL. PLEASE EXPLAIN
  
 5. IN REFERENCE TO COMMENT #1, CORRELATE DRAWING
 MATCHLINES ACCORDINGLY.
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722