2009-07-10 14:10:09 | REVIEW #: 1ST |
| ACTION: DENIED |
| |
| FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS |
| FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| |
| 1. VALUATION AS STATED ON PERMIT APPLICATION APPEARS TO |
| BE TOO LOW. THE VALUE STATED ON APPLICATION SHALL |
| INCLUDE ALL LABOR, MATERIALS, EQUIPMENT, DESIGN COSTS, |
| ETC. ASSOCIATED WITH THE PROPOSED SCOPE OF WORK. THIS |
| SHALL INCLUDE ANY AND ALL OWNER SUPPLIED MATERALS AND |
| EQUIPMENT. IT DOES NOT APPEAR THAT THE DUST COLLECTOR |
| ITSELF AND RELATED INSTALLATION COSTS ARE INCLUDED IN |
| THE STATED VALUE. PLEASE CORRECT AND RESUBMIT WITH |
| ADJUSTED VALUE. |
| |
| 2. DUST CLOOECTORS INSTALLED IN WOODWORKING FACILITIES |
| SHALL CONFORM TO NFPA 664-02 IN ACCORDANCE WITH FBC-M |
| 511.4. NFPA 664 ALLOWS TWO COMPLIANCE OPTIONS. PLEASE |
| INDICATE WHICH COMPLIANCE OPTION IS TO BE USED BY THE |
| DESIGN PROFESSIONAL PER NFPA 664 SECTION 4.3.1. PROVIDE |
| ALL DOCUMENTATION NECESSARY TO SUPPORT THE COMPLIANCE |
| METHOD CHOSEN AND DEMONSTRATE COMPLIANCE WITH THE SAME. |
| A COMPLETE REVIEW OF THE DUST COLLECTION SYSTEM CAN NOT |
| BE PERFORMED AT THIS TIME. |
| |
| 3. PLEASE INDICATE THE CURRENT USE OF THE PROPOSED |
| SPACE PRIOR TO CONVERSION TO WOODWORKING FACILITY. USE |
| OF THIS SPACE FOR WOODWORKING MAY CONSTITUTE A CHANGE |
| OF OCCUPANCY IN ACCORDANCE WITH FBC-EB SECTION 901. |
| |
| 4. NO INSTALLATION DETAILS OR INFORMATION WAS PROVIDED |
| FOR THE DUST COLLECTOR BEING INSTALLED OUTDOORS. |
| PROVIDE INSTALLATION DETAILS SHWOING HOW THE COLLECTOR, |
| DUCTWORK AND SUPPORTS ARE DESIGNED AND INSTALLED FOR |
| WIND RESISTANCE IN ACCORDANCE WITH FBC-M 301.12. |
| |
| 5. PROVIDE A SITE PLAN OF THE PROPOSED LOCATION OF THE |
| DUST COLLECTOR SHOWING DIDTANCES FROM PROPERTY LINES |
| AND ADJACENT BUILDINGS. ALSO, PROVIDE AN ELEVATION VIEW |
| OF THE COLLECTOR LOCATION WITH ELEVATIONS SHOWN IN |
| RELATION TO GRADE AND ADJACENT BUILDINGS. THIS IS |
| NEEDED TO DEMONSTRATE COMPLIANCE WITH THE DISCHARGE AND |
| CLEARANCE REQUIREMENTS OF FBC-M SECTIONS 510 AND 511. |
| |
| 6. PERMIT APPLICATION INDICATES THE SITE OF THE PROPSED |
| WORK IS AT 1221 ANDREWS ROAD. THE ADDRESS ON PLANS |
| INDICATES THE SITE IS 2900 HILLSBORO ROAD. PLEASE |
| COORDINATE ADDRESS ON PLANS WITH THE PERMIT APLICATION, |
| SHOWING THE CORRECT, ACTUAL ADDRESS OF THE PROPOSED |
| WORK ON BOTH. |
| |
| IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: |
| RONALD J. REGUEIRO |
| 561.805.6719 |
| [email protected] |