Plan Review Notes For Permit 09060572 |
Permit Number |
09060572 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2009-06-24 11:16:58 | RESIDENTIAL (R3) RE-ROOF, BUILDING REVIEW CHECKLIST. | | 2007 FL RESIDENTIAL CODE WITH 2009 REVISIONS. | | | | 1- ACCORDING TO THE 2009 REVISIONS TO THE 2007 FLORIDA | | RESIDENTIAL CODE THIS BUILDING IS LOCATED ON EXPOSURE | | "C" (SEC. R301.2.1.4.3). FLAT ROOF PRODUCT APPROVAL | | FL1654-R4 AND SPECIFIC SYSTEM SELECTED W-32 INDICATES | | THAT THE MAX. DESIGN PRESSURES FOR THIS SYSTEM IS | | -90PSF. IF BUILDING IS LOCATED ON EXPOSURE "C" THE | | DESIGN PRESSURES ARE HIGHER THAN -90PSF AT CORNER | | AREAS. NOTE # 7 ON SHEET 2 OF 33 OF PRODUCT APPROVAL | | SUBMITTED STATES THAT NO RATIONAL ANALYSIS IS PERMITTED | | TO INCREASE THE DESIGN PRESSURES. | | NEED TO SPECIFY FULLY BONDED ASSEMBLY WITH DESIGN | | PRESSURES THAT MEETS THE CALCULATED DESIGN PRESSURES | | FOR EXPOSURE 'C" OR SELECT ASSEMBLY WITH MECHANICALLY | | ATTACHED BASE SHEET. THIS SECOND OPTION REQUIRES SIGNED | | AND SEALED CALCULATIONS DONE BY A DESIGN PROFESSIONAL. | | SEE NOTE #6 ON SHEET 2 OF 33. | | | | | | JULIO GOMEZ | | BUILDING PLANS EXAMINER | | (561)805-6712 |
|