Plan Review Notes For Permit 09060533 |
Permit Number |
09060533 |
|
Review Stop |
FIRE |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2009-07-16 14:20:49 | *****DENIED***** | | | | THE FOLLOWING COMMENT FROM THE PREVIOUS FIRE PLAN | | REVIEW STILL NEEDS TO BE ADDRESSED: | | | | 1. PLEASE PROVIDE A FLOOR PLAN SHOWING THE LAYOUT OF | | ALL EQUIPMENT PROPOSED WITHIN THIS SCOPE OF WORK OR | | PROVIDE A LETTER OR ADDENDUM TO THE APPROPIATE PLAN | | SHEET THAT THE AS-BUILTS DRAWINGS SHALL BE SUBMITTED | | AND APPROVED BY CONSTRUCTION SERVICES DEPARTMENT/FIRE | | PLAN REVIEW PRIOR TO THE FINAL FIRE ALARM INSPECTION. | | | | THE FOLLOWING NEW COMMENTS ARE TO BE ADDRESSED: | | | | 2. SINCE THE SCOPE OF WORK IS GREATER THAN $2500.00, | | THE APPLICANT SHALL FILE WITH WITH THE IOSSUING | | AUTHORITHY EITHER A CERTIFIED COPY OF THE RECORDED | | NOTICE OF COMMENCEMENT OR A NOTORIZED STATEMENT THAT | | THE NOTICE OF COMMENCEMENT HAS BEEN FILED FOR | | RECORDING, ALONG WITH A COPY THEREOF. | | | | 3. SINCE THE SCOPE OF WORK IS GREATER THAN $5000.00, | | ALL PLAN SHEETS ARE TO BE SEALED, SIGNED, AND DATED BY | | THE ENGINEER OF RECORD (AS PER FAC 61G15-23.002 AND/OR | | FS 472.025) WHOSE INFORMATION IS IN THE TITLE BLOCK. | | SEE SHEET FA-02 | | | | 4. THE SUITE NUMBER SHALL BE INCLUDED WITH THE ADDRESS | | LOCATED IN THE TITLS BLOCK OF EACH SUBMITTED PLAN | | SHEET. | | | | 5. DRAWINGS FA-1 AND FA-2 ARE BOTH LISTED AS 1 OF 1 | | SHEET NUMBERS. PLEASE AMEND TO 1 OF 2 AND 2 OF 2 | | DRAWING/SHEET NUMBERS. | | | | | | |
|