Plan Review Notes
Plan Review Notes For Permit 09060533
Permit Number 09060533
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2009-06-24 11:22:08***DENIED***
  
 1) PLEASE PROVIDE A FLOOR PLAN SHOWING THE LAYOUT OF
 ALL EQUIPMENT PROPOSED WITHIN THIS SCOPE OF WORK.
  
 2) WORK TO COMPLY WITH 2002, NFPA 72.
  
 3) LIFE SAFETY TO COMPLY WITH 2006, NFPA 101.
  
 4) DUCT SMOKE DETECTORS SHALL INITIATE A GENERAL FIRE
 ALARM IN ACCORDANCE WITH LOCAL REQUIREMENTS.
  
  
 MIKE WENNERGRE, ASST. FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756