Plan Review Notes For Permit 09060498
Permit Number 09060498
Review Stop G
Sequence Number 1
Notes
Date Text
2009-06-24 08:38:55DENIED
 REFERENCE:
 FBC-2007 RESIDENTIAL
 FBC-2007 CHAPTER 1
  
 A. THE FOLLOWING INFORMATION IS REQUIRED FOR A GAS
 PERMIT:
  
 1. TYPE OF GAS, (LP OR NATURAL).
  
 2. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2007 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
  
 3. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2007 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33) OR RESIDENTIAL CODE SECTIONS G2412.8 THRU
 G2413.6.1 AND TABLES G2413.4(1) THRU 2413.4(8). --
 TOTAL NOT SHOWN.
  
 4. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2007 FUEL GAS CODE SEC 402.2 & RESIDENTIAL CODE
 SEC. G2413.2.
  
 5. PER FBC-2007 FUEL GAS, SECTION 409.4 MP REGULATOR
 VALVES: A LISTED SHUTOFF VALVE SHALL BE INSTALLED
 IMMEDIATELY AHEAD OF EACH MP REGULATOR. A UNION IS
 REQUIRED DOWNSTREAM OF THE SHUT OFF VALVE FOR THE HOUSE
 REGULATOR.
  
 6. SUBMIT MANUF SPEC SHEETS FOR THE REGULATORS.
 INDICATE MODEL OF REGULATOR AS WELL AS THE OUTPUT
 CAPACITY OF THE REGULATORS. THE REGULATORS SHALL BE
 LISTED. SECTION 106.1.2 (MORE INFORMATION REQUIRED).
  
 B. THE FOLLOWING INFORMATION IS REQUIRED FOR THE POOL
 HEATER:
  
 1. FBC-2007 SEC. 424.2.14.1, OR
 FBCR-2007 SEC. R4101.14.1 SWIMMING POOL
 WATER HEATERS SHALL BEAR THE LABEL OF A
 RECOGNIZED TESTING AGENCY. (MANUFACTURE
 SHEETS REQUIRED, PLEASE SUBMIT).
  
 2. FBC-2007 SEC. 424.2.14.2, OR
 FBCR-2007 SEC. R4101.14.2 WATER
 RETENTION, PROVIDE A POSITIVE MEANS OF
 RETAINING WATER IN THE HEATER WHEN PUMP
 IS SHUT OFF. (MANUFACTURE SHEETS
 REQUIRED, PLEASE SUBMIT).
  
 C. 1. THE VALUE ON THE PERMIT APPLICATION APPEARS LOW.
 THE VALUE ON THE PERMIT APPLICATION MUST INCLUDE THE
 TOTAL COST OF LABOR, MATERIALS AND DESIGN.
 PER (W.P.B AS AMENDED) SECTION 108.3 BUILDING PERMIT
 VALUATION. IF, IN THE OPINION OF THE BUILDING OFFICIAL,
 THE CLAIMED VALUATION OF BUILDING, ALTERATION,
 STRUCTURAL, ELECTRICAL, GAS, MECHANICAL OR PLUMBING
 SYSTEMS APPEARS TO BE UNDERESTIMATED ON THE
 APPLICATION, THE PERMIT SHALL BE DENIED. -- MARSHALL &
 SWIFT INDICATES THE GAS POOL HEATER TO BE APPROX.
 $3000. SO WITH THE PIPING, VALVES, REGULATORS & LABOR
 THE JOB WILL BE ABOUT $4,000 TOTAL. A NOTICE OF
 COMMENCEMENT WILL BE REQUIRED PER FS 713.3.
  
 D. A MINIMUM OF TWO SETS OF PLANS IS REQUIRED WITH EACH
 APPLICATION FOR PERMIT. SECTION 106.1. ONLY ONE SET OF
 PLANS HAS BEEN SUBMITTED FOR REIVEW.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  