Plan Review Notes For Permit 09060399 |
Permit Number |
09060399 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2009-07-07 15:38:51 | *****PARTIAL APPROVAL***** | | | | PLAN SHEET FP1.01 WAS STAMPED, INITIALED, AND DATED; | | HOWEVER SHEET E1.01 TO BE FIRE-STAMPED WHEN THE | | ELETRICAL EXAMINER COMMENTS AS WELL AS THE FOLLOWING | | HAVE BEEN ADDRESSED: | | | | 1. ON SHEET E1.01, SMOKE DETECTORS (SD)ARE SHOWN. | | PLEASE BE ADVISED THAT SMOKE ALARMS ARE TIED INTO THE | | BUILDING'S FIRE ALARM SYSTEM. IF THESE DEVICES SOUND | | ONLY WITHIN THE INDIVIDUAL DWELLING UNIT AND DOES NOT | | ACTUATE THE BUILDING FIRE ALARM SYSTEM, SMOKE ALARMS | | (SA) INSTEAD OF SMOKE DETECTORS (SD) SHOULD BE | | LEGENDED/SYMBOLED. | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|