Plan Review Notes
Plan Review Notes For Permit 09060399
Permit Number 09060399
Review Stop E
Sequence Number 1
Notes
Date Text
2009-07-04 09:11:12 
 ** DENIED REVIEW **
  
 1) NOTE: PLEASE BE SURE PLANS CONTAIN THE CODES UNDER
 ADOPTION BY THE STATE OF FLORIDA.
 ELECTRICAL PLANS THE * LATEST EDITION* WHICH IS NOT
 PERMITTED. ALL PLANS SHALL CONTAIN THE MINIMUM CODES IN
 WHICH THE DESIGN IS UNDER.
 PLEASE SEE THAT THE FOLLOWING FOR THIS PROJECT SHALL BE
 AS FOLLOWS.
 COVER SHEET HAS CONFLICTING SUPPLEMENTS FOR THE 2007
 FBC. ONE AREA SHOWS 2009 AND THE OTHER 2007.
  
 ELECTRICAL SHALL CONTAIN:
 2005 NFPA-70
 2006 NFPA-101
 2002 NFPA-72
  
  
 PLEASE SEE FAC 69A-60.004 AND 69A-3.012.
 FS 553.73 AND 2007 FBC WITH 2009 SUPPLEMENTS
  
 2) NOTE:
  
 3) NOTE: PLEASE SEE RISER. RISER SHOWS NEW BRANCH
 CIRCUIT #42, HOWEVER PER THE PANEL SCHEDULE SUBMITTED
 CIRCUIT #42 IS SHOWN BLANK.
 PLEASE COORDINATE PLANS FOR ALL.
 408.4.
  
 4) NOTE: PLEASE SEE 422.13 OF THE 2005 NEC. WATER
 HEATER LOAD IS CONSIDERED A CONTINUOUS LOAD WHICH
 REQUIRES LOAD TO BE SHOWN AND FIGURED AT 125%.
  
 5) NOTE:
  
 6) NOTE: THE LOAD CALCULATIONS SHOWN ON PLANS ARE BASED
 ON A RESIDENTIAL USE. CODE SECTIONS ON LOAD
 CALCULATIONS ARE NOT FROM THE 2005 NEC. PLEASE SEE
 PLANS FOR EXAMPLE: 220.4,220.30. THE 2005 NEC HAS BEEN
 THE STATE ADOPTED CODE SINCE DECEMBER 8TH, 2006. PLANS
 STATE THE DESIGN IS UNDER THE *LATEST EDITION* OF THE
 NEC. PLEASE KNOW EVEN IF THIS WAS THE CASE AND THE 2008
 NEC WAS ADOPTED BY THE STATE, THERE IS NO 220.30, 220.4
 IN THE 2008 CODE.
  
 *** KEEP IN MIND LOADS FOR OFFICE EQUIPMENT AS OFFICE
 FOR EXAMPLE IS SHOWING ALL ON EXISTING CIRCUIT #17. ANY
 NEW COPIERS OR EQUIPMENT WHICH MAY EXCEED THE RATING OF
 THIS RESIDENTIAL BRANCH CIRCUIT?
  
 PLEASE SEE NEC 220 UNDER THE 2005 NEC.
 SINCE USE IS STILL SHOWN AS COMPLETELY RESIDENTIAL.
  
 7) NOTE: ALL CIRCUITS SHALL BE SPECIFIC ON PLANS.
 STATING GENERAL LIGHTS, OR GENERAL RECEPTACLES IS NOT
 PERMITTED. PLEASE SEE COMMENTARY UNDER THE 2005 NEC IN
 408.4
 PLEASE SEE ITEMS SUCH AS CIRCUIT #17.
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  