2009-07-04 09:11:12 | |
| ** DENIED REVIEW ** |
| |
| 1) NOTE: PLEASE BE SURE PLANS CONTAIN THE CODES UNDER |
| ADOPTION BY THE STATE OF FLORIDA. |
| ELECTRICAL PLANS THE * LATEST EDITION* WHICH IS NOT |
| PERMITTED. ALL PLANS SHALL CONTAIN THE MINIMUM CODES IN |
| WHICH THE DESIGN IS UNDER. |
| PLEASE SEE THAT THE FOLLOWING FOR THIS PROJECT SHALL BE |
| AS FOLLOWS. |
| COVER SHEET HAS CONFLICTING SUPPLEMENTS FOR THE 2007 |
| FBC. ONE AREA SHOWS 2009 AND THE OTHER 2007. |
| |
| ELECTRICAL SHALL CONTAIN: |
| 2005 NFPA-70 |
| 2006 NFPA-101 |
| 2002 NFPA-72 |
| |
| |
| PLEASE SEE FAC 69A-60.004 AND 69A-3.012. |
| FS 553.73 AND 2007 FBC WITH 2009 SUPPLEMENTS |
| |
| 2) NOTE: |
| |
| 3) NOTE: PLEASE SEE RISER. RISER SHOWS NEW BRANCH |
| CIRCUIT #42, HOWEVER PER THE PANEL SCHEDULE SUBMITTED |
| CIRCUIT #42 IS SHOWN BLANK. |
| PLEASE COORDINATE PLANS FOR ALL. |
| 408.4. |
| |
| 4) NOTE: PLEASE SEE 422.13 OF THE 2005 NEC. WATER |
| HEATER LOAD IS CONSIDERED A CONTINUOUS LOAD WHICH |
| REQUIRES LOAD TO BE SHOWN AND FIGURED AT 125%. |
| |
| 5) NOTE: |
| |
| 6) NOTE: THE LOAD CALCULATIONS SHOWN ON PLANS ARE BASED |
| ON A RESIDENTIAL USE. CODE SECTIONS ON LOAD |
| CALCULATIONS ARE NOT FROM THE 2005 NEC. PLEASE SEE |
| PLANS FOR EXAMPLE: 220.4,220.30. THE 2005 NEC HAS BEEN |
| THE STATE ADOPTED CODE SINCE DECEMBER 8TH, 2006. PLANS |
| STATE THE DESIGN IS UNDER THE *LATEST EDITION* OF THE |
| NEC. PLEASE KNOW EVEN IF THIS WAS THE CASE AND THE 2008 |
| NEC WAS ADOPTED BY THE STATE, THERE IS NO 220.30, 220.4 |
| IN THE 2008 CODE. |
| |
| *** KEEP IN MIND LOADS FOR OFFICE EQUIPMENT AS OFFICE |
| FOR EXAMPLE IS SHOWING ALL ON EXISTING CIRCUIT #17. ANY |
| NEW COPIERS OR EQUIPMENT WHICH MAY EXCEED THE RATING OF |
| THIS RESIDENTIAL BRANCH CIRCUIT? |
| |
| PLEASE SEE NEC 220 UNDER THE 2005 NEC. |
| SINCE USE IS STILL SHOWN AS COMPLETELY RESIDENTIAL. |
| |
| 7) NOTE: ALL CIRCUITS SHALL BE SPECIFIC ON PLANS. |
| STATING GENERAL LIGHTS, OR GENERAL RECEPTACLES IS NOT |
| PERMITTED. PLEASE SEE COMMENTARY UNDER THE 2005 NEC IN |
| 408.4 |
| PLEASE SEE ITEMS SUCH AS CIRCUIT #17. |
| |
| ** IMPORTANT ** |
| ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| INTO TWO SETS/FOLDERS/BINDERS ETC. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| ANY DELAYS. |
| |
| IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| CONTACT THIS REVIEWER. |
| |