2009-06-15 14:46:53 | RE-ROOF BUILDING REVIEW CHECKLIST. |
| 2007 FBC WITH 2009 REVISIONS. |
| |
| 1- REVISE RAS 117 CALCULATIONS FOR FLAT ROOF SYSTEM: |
| A) ENGINEER TO REVISE DESIGN PRESSURES. THIS BUILDING |
| IS LOCATED ON EXPOSURE "C" NOT "B". |
| |
| B) REVISE NAIL ENHANCING AT PERIMETER AND CORNER AREAS. |
| COORDINATE WITH ITEM 1A ABOVE. |
| |
| 2- CLARIFY HOW ARE REPAIRS (COATING) GOING TO BE DONE |
| ON FLAT ROOF SHOWN ON SKETCH ON SHEET 5 SUBMITTED. IS |
| THIS A ROOF OVER?. PROVIDE CORRESPONDING PRODUCT |
| APPROVAL FOR RECOVERY OR ROOF OVER APPLICATIONS. |
| |
| 3- PROVIDE PRODUCT APPROVAL FOR: |
| A) SELF-ADHERED UNDERLAYMENTS TO BE ISSUED. |
| |
| B) POLYFOAM TO BE USED IN CONCRETE TILE. SEE TILE |
| PRODUCT APPROVAL FOR LISTED TYPES. |
| |
| C) ROOF TILE. FLORIDA PRODUCT APPROVAL FL601-R3 |
| SUBMITTED IS MISSING THE NOA 07-0711.03 THAT WAS |
| SUBMITTED TO GET THE FLORIDA PRODUCT APPROVAL. |
| |
| D) COPPER PANELS THAT RESIST THE UPLIFT PRESSURES |
| CALCULATED FOR ROOF ZONE 2 AND ROOF ZONE 3. NOA |
| 07-0822.05 SUBMITTED IS GOOD FOR MAX. DESIGN PRESSURE |
| OF -76.75PSF. RATIONAL ANALYSIS IS NOT ALLOWED. SEE |
| SYSTEM LIMITATION #1 ON SHEET 4 OF NOA SUBMITTED. |
| (NOTE: SAME COMMENT APPLIES TO FLORIDA PRODUCT APPROVAL |
| FL10601-R2 SUBMITTED). |
| ***NOTE: THIS BUILDING IS LOCATED ON EXPOSURE "C". |
| THEREFORE DESIGN PRESSURES ARE HIGHER THAN THOSE SHOWN |
| ON THIS PRODUCT APPROVAL. |
| |
| 4- SEPARATE PERMIT FOR A/C ROOF TOP UNITS IS REQUIRED |
| TO COMPLY WITH SEC. 301.12 OF 2007 FLORIDA MECHANICAL |
| CODE. SLEEPERS ARE NOT ALLOWED. COORDINATE WITH HAROLD |
| MOSER (561)805-6732. |
| |