2009-06-15 14:46:53RE-ROOF BUILDING REVIEW CHECKLIST.
 2007 FBC WITH 2009 REVISIONS.
  
 1- REVISE RAS 117 CALCULATIONS FOR FLAT ROOF SYSTEM:
 A) ENGINEER TO REVISE DESIGN PRESSURES. THIS BUILDING
 IS LOCATED ON EXPOSURE "C" NOT "B".
  
 B) REVISE NAIL ENHANCING AT PERIMETER AND CORNER AREAS.
 COORDINATE WITH ITEM 1A ABOVE.
  
 2- CLARIFY HOW ARE REPAIRS (COATING) GOING TO BE DONE
 ON FLAT ROOF SHOWN ON SKETCH ON SHEET 5 SUBMITTED. IS
 THIS A ROOF OVER?. PROVIDE CORRESPONDING PRODUCT
 APPROVAL FOR RECOVERY OR ROOF OVER APPLICATIONS.
  
 3- PROVIDE PRODUCT APPROVAL FOR:
 A) SELF-ADHERED UNDERLAYMENTS TO BE ISSUED.
  
 B) POLYFOAM TO BE USED IN CONCRETE TILE. SEE TILE
 PRODUCT APPROVAL FOR LISTED TYPES.
  
 C) ROOF TILE. FLORIDA PRODUCT APPROVAL FL601-R3
 SUBMITTED IS MISSING THE NOA 07-0711.03 THAT WAS
 SUBMITTED TO GET THE FLORIDA PRODUCT APPROVAL.
  
 D) COPPER PANELS THAT RESIST THE UPLIFT PRESSURES
 CALCULATED FOR ROOF ZONE 2 AND ROOF ZONE 3. NOA
 07-0822.05 SUBMITTED IS GOOD FOR MAX. DESIGN PRESSURE
 OF -76.75PSF. RATIONAL ANALYSIS IS NOT ALLOWED. SEE
 SYSTEM LIMITATION #1 ON SHEET 4 OF NOA SUBMITTED.
 (NOTE: SAME COMMENT APPLIES TO FLORIDA PRODUCT APPROVAL
 FL10601-R2 SUBMITTED).
 ***NOTE: THIS BUILDING IS LOCATED ON EXPOSURE "C".
 THEREFORE DESIGN PRESSURES ARE HIGHER THAN THOSE SHOWN
 ON THIS PRODUCT APPROVAL.
  
 4- SEPARATE PERMIT FOR A/C ROOF TOP UNITS IS REQUIRED
 TO COMPLY WITH SEC. 301.12 OF 2007 FLORIDA MECHANICAL
 CODE. SLEEPERS ARE NOT ALLOWED. COORDINATE WITH HAROLD
 MOSER (561)805-6732.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 (561)805-6712