2009-09-10 10:00:17 | ** PROVISO ** |
| |
| ** ALL OF THE FOLLOWING COMMENTS NEED TO BE ADDRESSED |
| BEFORE ANY FINAL ELECTRICAL INSPECTION. |
| ** OTHER ITEMS REVISED ON PLANS WHICH ARE NOT PART OF |
| PROVISO, SHALL BE REVISED AND SUBMITTED BEFORE ROUGH |
| ELECTRICAL INSPECTION. |
| **** |
| *PROVISO IS GIVEN AT THE REQUEST OF THE DESIGNER AND |
| WILL BE COMPLETELY AT THE RISK OF CONTRACTOR, |
| ELECTRICAL CONTRACTOR AND DESIGNER OF RECORD. |
| |
| 1) NOTE: PLANS NEED TO SHOW ALL CIRCUITING FOR LIGHTING |
| AND RECEPTACLES. THIS WILL NEED TO BE SUBMITTED AND |
| COORDINATE WITH PANEL SCHEDULES WHICH HAVE NOT YET BEEN |
| SUBMITTED AND SHOWN ON RECORD SET OF PLANS. |
| 408.4,310.16,240.4 ETC |
| |
| 2) NOTE: ALL FINAL LOAD CALCULATIONS FOR ALL LIGHTING, |
| RECEPTACLES AND OTHER LOADS SHALL BE COMPLETED ON |
| RECORD SET OF PLANS. |
| PLEASE SEE ALL OF NEC 220 FOR CODES SUCH AS |
| 220.12,220.14,220.42,220.44 ETC |
| PLEASE SEE 215.3,230.42 ETC FOR CONTINUOUS LOADS. |
| |
| 3) NOTE: PANEL AND TAPPED CONDUCTORS ON THE SECONDARY |
| SIDE OF COMPUTER TRANSFORMER SHALL MEET 240.21,408.36, |
| 240.4,310.16 ETC |
| THE PLANS ARE NOT COMPLETE WITH CONDUCTORS ETC SHOWN |
| FOR EXISTING. THERE MAY BE CODE COMPLIANCE COMMENTS |
| WHICH CAN NOT BE REVIEWED OR MADE AT THIS TIME. THIS |
| MAY CREATE CHANGES NEEDED IN FIELD. |
| |
| |
| IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| CONTACT THIS REVIEWER. |
| |