Plan Review Notes
Plan Review Notes For Permit 09060324
Permit Number 09060324
Review Stop E
Sequence Number 2
Notes
Date Text
2009-09-10 10:00:17** PROVISO **
  
 ** ALL OF THE FOLLOWING COMMENTS NEED TO BE ADDRESSED
 BEFORE ANY FINAL ELECTRICAL INSPECTION.
 ** OTHER ITEMS REVISED ON PLANS WHICH ARE NOT PART OF
 PROVISO, SHALL BE REVISED AND SUBMITTED BEFORE ROUGH
 ELECTRICAL INSPECTION.
 ****
 *PROVISO IS GIVEN AT THE REQUEST OF THE DESIGNER AND
 WILL BE COMPLETELY AT THE RISK OF CONTRACTOR,
 ELECTRICAL CONTRACTOR AND DESIGNER OF RECORD.
  
 1) NOTE: PLANS NEED TO SHOW ALL CIRCUITING FOR LIGHTING
 AND RECEPTACLES. THIS WILL NEED TO BE SUBMITTED AND
 COORDINATE WITH PANEL SCHEDULES WHICH HAVE NOT YET BEEN
 SUBMITTED AND SHOWN ON RECORD SET OF PLANS.
 408.4,310.16,240.4 ETC
  
 2) NOTE: ALL FINAL LOAD CALCULATIONS FOR ALL LIGHTING,
 RECEPTACLES AND OTHER LOADS SHALL BE COMPLETED ON
 RECORD SET OF PLANS.
 PLEASE SEE ALL OF NEC 220 FOR CODES SUCH AS
 220.12,220.14,220.42,220.44 ETC
 PLEASE SEE 215.3,230.42 ETC FOR CONTINUOUS LOADS.
  
 3) NOTE: PANEL AND TAPPED CONDUCTORS ON THE SECONDARY
 SIDE OF COMPUTER TRANSFORMER SHALL MEET 240.21,408.36,
 240.4,310.16 ETC
 THE PLANS ARE NOT COMPLETE WITH CONDUCTORS ETC SHOWN
 FOR EXISTING. THERE MAY BE CODE COMPLIANCE COMMENTS
 WHICH CAN NOT BE REVIEWED OR MADE AT THIS TIME. THIS
 MAY CREATE CHANGES NEEDED IN FIELD.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  