Plan Review Notes For Permit 09060324 |
Permit Number |
09060324 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2009-07-06 09:24:37 | DENIED | | REFERENCE: | | FBC-2007 PLUMBING | | FBC-2007 CHAPTER 1 | | FBC-2007 CHAPTER 11 | | | | 1. SHTS A1.1 & A6.1 SHOW THE CLEAR FLOOR SPACE REQUIRED | | PER SECTION 11-4.24.5. | | | | 2. SHT A3.1 SHOW COMPLIANCE WITH THE FOLLOWING: | | A. 11-4.24.4 SINK DEPTH | | B. 11-4.24.7 FAUCTES | | | | 3. SHT MEP-1 THE AAV IS NOT APPROVED IN THE CEILING | | UTILIZED AS A PLENUM. SECTION 917.8. | | | | 4. SUBMIT A WATER ISOMETRIC RISER DIAGRAM. SECTION | | 106.3.5.1.3(3)(10)(13). SHOW ALL PIPE SIZES, VALVES | | AND, (WHERE REQUIRED), WATER HAMMER ARRESTORS. SECTIONS | | 604.3, 604.9 & 606.2. | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | THE REVISION & REMOVE & REPLACE ANY | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | WITH A DESCRIPTION OF THE REVISION MADE, | | IDENTIFYING THE SHEET OR SPECIFICATION | | PAGE WHERE THE CHANGES CAN BE FOUND | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | ONE SET OF THEM LOOSELY ON TOP OF THE | | COLLATED PLANS TO BE REVIEWED. | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 805-6731 | | E-MAIL [email protected] | | |
|