Plan Review Notes
Plan Review Notes For Permit 09060324
Permit Number 09060324
Review Stop M
Sequence Number 1
Notes
Date Text
2009-07-20 10:46:49REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PROVIDE VENTILATION CALCULATIONS FOR ALL
 RECONFIGURED SPACES PER FBC-EB 709.1.
  
 2. PROVIDE CFM ON PLAN TO SHOW PROPER AIR DISTRIBUTION
 IN ALL HABITABLE SPACES PER FBC-EB 711.1, FBC-B
 13-410.AB.4, FBC-M 403.3.4.
  