 ** DENIED PLANS REVIEW **
  
 1) NOTE: PLEASE SEE THAT THE FOLLOWING CODES NEED TO BE
 UPDATED. THE COVER SHEET DOES LIST MOST OF THE CURRENT
 ADOPTED CODES HOWEVER NOT ALL.
 PLEASE SEE THE FOLLOWING.
  
 2006 NFPA-101. THIS EDITION WAS ADOPTED DECEMBER 31ST
 2008. FAC 69A-60.004
 2007 FLORIDA FIRE PREVENTION CODE.
  
 ALL PLANS SHALL CONTAIN MINIMUM DESIGN CODES.
  
 2) NOTE: PLEASE COMPLETE CIRCUITING ON PLANS SHOWING
 MINIMUM CODE COMPLIANCE. PLEASE COORDINATE WITH PANEL
 SCHEDULES TO BE SUBMITTED.
 THERE ARE NUMEROUS ITEMS FOR MINIMUM CODE COMPLIANCE
 WHICH CAN NOT BE REVIEWED AT THIS TIME.
 408.4,310.16,240,220 ETC PLEASE BE SURE TO CIRCUIT
 EMERGENCY AND EXIT LIGHTS PER 700.12F
  
 EVERYTHING IS SHOWN AS NEW. PLEASE PLACE ITEMS ABOVE ON
 PLANS. THE PLANS STATES MANY ITEMS ARE NO CLEAR ON
 PANELS YET LOADS FOR NEW CIRCUITS, RECEPTACLES ETC
 SHOULD BE KNOWN AT THIS TIME.
 THE PLANS ALSO STATE THE *ENTIRE* 8TH FLOOR IS FED FROM
 ONE 125AMP PANEL. IF THIS IS THE CASE THERE IS CONCERN
 ON LOADS ON EQUIPMENT. PLANS SHOW THREE SEPARATE PANELS
 ???
 ** ALL TENANTS ARE FED FROM ONE METER?
  
  
 4) NOTE: PLEASE SEE 13-415.AB.5 FOR MINIMUM CODE
 COMPLIANCE REQUIRED FOR LIGHTING PERFORMANCE
 CALCULATIONS.
 ** PLEASE BE SURE TO COMPLETE A FIXTURE LEGEND WHICH
 STATES THE SPECIFIC FIXTURES.
  
  
 *** ALL LOW VOLTAGE WORK SHALL BE UNDER SEPARATE
 PERMITS.
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved