2009-07-05 14:07:09 | |
| ** DENIED PLANS REVIEW ** |
| |
| 1) NOTE: PLEASE SEE THAT THE FOLLOWING CODES NEED TO BE |
| UPDATED. THE COVER SHEET DOES LIST MOST OF THE CURRENT |
| ADOPTED CODES HOWEVER NOT ALL. |
| PLEASE SEE THE FOLLOWING. |
| |
| 2006 NFPA-101. THIS EDITION WAS ADOPTED DECEMBER 31ST |
| 2008. FAC 69A-60.004 |
| 2007 FLORIDA FIRE PREVENTION CODE. |
| |
| ALL PLANS SHALL CONTAIN MINIMUM DESIGN CODES. |
| |
| 2) NOTE: PLEASE COMPLETE CIRCUITING ON PLANS SHOWING |
| MINIMUM CODE COMPLIANCE. PLEASE COORDINATE WITH PANEL |
| SCHEDULES TO BE SUBMITTED. |
| THERE ARE NUMEROUS ITEMS FOR MINIMUM CODE COMPLIANCE |
| WHICH CAN NOT BE REVIEWED AT THIS TIME. |
| 408.4,310.16,240,220 ETC PLEASE BE SURE TO CIRCUIT |
| EMERGENCY AND EXIT LIGHTS PER 700.12F |
| |
| EVERYTHING IS SHOWN AS NEW. PLEASE PLACE ITEMS ABOVE ON |
| PLANS. THE PLANS STATES MANY ITEMS ARE NO CLEAR ON |
| PANELS YET LOADS FOR NEW CIRCUITS, RECEPTACLES ETC |
| SHOULD BE KNOWN AT THIS TIME. |
| THE PLANS ALSO STATE THE *ENTIRE* 8TH FLOOR IS FED FROM |
| ONE 125AMP PANEL. IF THIS IS THE CASE THERE IS CONCERN |
| ON LOADS ON EQUIPMENT. PLANS SHOW THREE SEPARATE PANELS |
| ??? |
| ** ALL TENANTS ARE FED FROM ONE METER? |
| |
| |
| 4) NOTE: PLEASE SEE 13-415.AB.5 FOR MINIMUM CODE |
| COMPLIANCE REQUIRED FOR LIGHTING PERFORMANCE |
| CALCULATIONS. |
| ** PLEASE BE SURE TO COMPLETE A FIXTURE LEGEND WHICH |
| STATES THE SPECIFIC FIXTURES. |
| |
| |
| *** ALL LOW VOLTAGE WORK SHALL BE UNDER SEPARATE |
| PERMITS. |
| |
| ** IMPORTANT ** |
| ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| INTO TWO SETS/FOLDERS/BINDERS ETC. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| ANY DELAYS. |
| |
| IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| CONTACT THIS REVIEWER. |
| |