Plan Review Notes For Permit 09060303 |
Permit Number |
09060303 |
|
Review Stop |
M |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2009-10-21 18:50:59 | REVISED M-101, M-102 DELTA 4 | | | | | | **REVISION REQUIRED** | | | | PAGE M-101: PLAN SHOWS EXHAUST OUTLETS SEPARATED BY | | LESS THAN 10' FROM FRESH AIR INTAKES. REVISE PLANS TO | | SHOW THESE OPENINGS TO BE MINIMUM 10 FEET APART IN | | ACCORDANCE WITH FBC-M 401.4. THIS IS THE SECOND TIME | | THIS CORRECTION HAS BEEN REQUESTED BY PROVISO. | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | RONALD J. REGUEIRO | | 561.805.6719 | | [email protected] |
|