Plan Review Notes
Plan Review Notes For Permit 09060303
Permit Number 09060303
Review Stop M
Sequence Number 2
Notes
Date Text
2009-10-02 15:55:46**PROVISO**
 REVISED M-101 AND M-102, DELTA 2
  
 EXHAUST AND INTAKE LOUVERS SHALL BE MINIMUM 10' APART
 PER FBC-M 401.5. PLAN SHOWS A MEASUREMENT OF 10'
 CENTER-TO-CENTER.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: