2009-08-05 14:04:27 | DENIED |
| REFERENCE: |
| FBC-2007 PLUMBING |
| |
| |
| 1. SEE COMMENTS 1, 1A & 1B BY THE BUILDING PLANS |
| REVIEWER AND COMMENT 2 BY THE ELECTRICAL PLANS |
| REVIEWER. THESE COMMENTS SHALL BE ADDRESSED PRIOR TO |
| PERMIT ISSUANCE. |
| |
| 2. SHT P-102 NOTE STATES IN PART "CONNECT NEW 4" |
| SANITARY LINE" BUT SHOWS A 6" SANITARY LINE. PLEASE |
| CLARIFY. SECTIONS 106.1.1 & 701.1. |
| |
| 3. SHT P-103 SANITARY RISER DIAGRAM DOES NOT REFLECT |
| THE FLOOR PLAN WHERE THE FLOOR DRAIN CONNECTS TO THE |
| BRANCH LINE WEST OF THE BOUTIQUE. THE FLOOR PLAN SHOWS |
| THE FLOOR DRAIN IN THE DOG ADOPTION ROOM CONNECTING |
| BETWEEN THE 2ND AND THIRD FLOOR DRAINS TO THE EAST OF |
| THE BRANCH LINE, BUT BETWEEN THE 1ST & 2ND FLOOR DRAINS |
| ON THE RISER DIAGRAM. PLEASE CORRELATE. SECTIONS |
| 106.1.1 & 701.1. |
| |
| 4. SHT P-203 A SHUT OFF VALVE IS REQUIRED ON THE WATER |
| SUPPLY LINE TO EACH HOSE BIBB. SECTION 606.2(2). |
| |
| 5. SHT P-300 PLUMBING NOTES NUMBER 13. AIR CHAMBERS ARE |
| NOT APPROVED. PDI-WH 201. PLEASE DELETE FROM NOTES. |
| |
| ***NOTE: THE COMMENTS 3 THRU 5 CAN BE PROVISO'D AND |
| REVISIONS CAN BE SUBMITTED FOR THESE COMMENTS.*** |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| ONE SET OF THEM LOOSELY ON TOP OF THE |
| COLLATED PLANS TO BE REVIEWED. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| REVIEW BY KEN STEVENS |