Plan Review Notes
Plan Review Notes For Permit 09060303
Permit Number 09060303
Review Stop M
Sequence Number 1
Notes
Date Text
2009-07-17 09:05:38**PROVISO**
  
 1. REVISE PLANS REMOVING FIRE DAMPERS FROM NON-RATED
 WALLS AS SHOWN ON M101. THERE ARE NO RATED WALL
 ASSEMBLES SHOWN BEING PENETRATED ON THIS PLAN. FBC-M
 607.1.1
  
 2. VERIFY PROPER SERVICE CLEARANCE FOR AHU-2 PER FBC-M
 304.1 AND 306.1.
  