Plan Review Notes
Plan Review Notes For Permit 09060303
Permit Number 09060303
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2009-07-21 08:38:13GRACE PAVILLION
 3100 NORTH MILITARY TRAIL
 PHASE II, INCLUDING HVAC UNITS, PLUMBING, AND FLAT WORK
  
 1. WRONG CODE REFERENCES NOTED ON PAGE CS-1.
  
 2. SEPARATE PLANS AND PERMITS REQUIRED FOR FIRE
 SPRINKLER SYSTEM REMODEL.
  
 3. ALL REQUIRED FIRE DAMPERS ARE TO BE DROP TESTED
 AFTER INSTALLATION.
  
 4. SEPARATE PLANS AND PERMITS REQUIRED FOR ANY FIRE
 ALARM SYSTEM REMODEL OR ADDITIONS.
  
 5. PLANS DO NOT ILLUSTRATE ILLUMINATED EXIT SIGNS OR
 PORTABLE FIRE EXTINGUISHER LOCATIONS.
  
 6. TWO HOUR RATED WALLS ARE DISPLAYED BUT COULD NOT
 LOCATE RATED DOOR INFORMATION.
  
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
 804-4709 PHONE
 804-4774 FAX