Plan Review Notes
Plan Review Notes For Permit 09060277
Permit Number 09060277
Review Stop B
Sequence Number 1
Notes
Date Text
2009-06-12 13:19:15RESIDENTIAL (R3) RE-ROOF, BUILDING REVIEW CHECKLIST.
 2007 FL. RESIDENTIAL CODE W/ 2009 REVISIONS.
  
 1- CLEARLY MARK ON NOA 07-0730.03 SUBMITTED FOR FLAT
 ROOF WHICH BASE SHEET FASTENING OPTION IS GOING TO BE
 INSTALLED ON SELECTED APPROVED ASSEMBLY. SEC. R301 OF
 2007 FLORIDA RESIDENTIAL CODE.
  
 2- PROVIDE RAS 117 CALCULATIONS FOR NAIL ENHANCING AT
 PERIMETER AND CORNER AREAS AS REQUIRED BY GENERAL
 LIMITATION #7.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712
  
  