2009-06-12 09:28:56 | ****CORRECTIONS**** |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| 561-805-6724 [email protected] |
| FBC FLORIDA BUILDING CODE 2007 |
| FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL |
| |
| 1. FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED FOR |
| THE DOOR, FAC9B72. LOCAL PRODUCT APPROVAL APPLICATION |
| IS AVAILABLE ON THE INTERNET AT |
| WWW.FLORIDABUILDING.ORG. |
| |
| 2. FBC1507.2.9.3, SEE FIRST OVERHANG OPTION. IT IS NOT |
| CLEAR HOW THE DRIP EDGE WILL PROPERLY BE INSTALLED |
| USING THIS OPTION. PLEASE PROVIDE A LEGIBLE DETAIL |
| SHOWING ALL COMPONENTS. |
| |
| 3. SHEATHING IS REQUIRED TO MEET MINIMUM REQUIREMENTS |
| OF FBC R TABLE 803.1. |
| |
| 4. 6D NAILS SPECIFIED ON SHEET 3, DOES NOT MEET MINIMUM |
| SHEATHING REQUIREMENTS, FBC R803.2.3.1. |
| |
| 5. THE ENGINEER'S SEAL REQUIRES A DATE, |
| FAC61G15-23.002. |
| |
| 6. CERTIFICATE OF AUTHORIZAITON REQUIRED TO PRACTICE |
| ENGINEERING THROUGH A COMPANY, FS471. TRUSS ENGINEERING |
| INCLUDES "RICHARD WEINGARDT CONSULTANTS." |
| |
| 7. ALL INFORMATION REQUIRED BY FAC61G15-23.002 ON EACH |
| SHEET (TRUSS ENGINEERING). |
| |
| 8. TRUSS ENGINEERING DESIGN SPECIFIES IBC, PLEASE |
| REVISE TO GOVERNING CODE. |
| |
| 9. ROOF PERMIT REQUIRED. |
| |
| 10. PLEASE INCLUDE DISTANCE FROM EXISTING HOUSE TO |
| PROPOSED NEW STRUCTURE, FBC R302.1. |
| |
| 11. IT IS NOT CLEAR HOW THE DOOR WILL COMPLY WITH FBC |
| R311.4.4. IS THIS DOOR OPERABLE FROM THE INSIDE? |
| |