2009-06-12 09:28:56****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED FOR
 THE DOOR, FAC9B72. LOCAL PRODUCT APPROVAL APPLICATION
 IS AVAILABLE ON THE INTERNET AT
 WWW.FLORIDABUILDING.ORG.
  
 2. FBC1507.2.9.3, SEE FIRST OVERHANG OPTION. IT IS NOT
 CLEAR HOW THE DRIP EDGE WILL PROPERLY BE INSTALLED
 USING THIS OPTION. PLEASE PROVIDE A LEGIBLE DETAIL
 SHOWING ALL COMPONENTS.
  
 3. SHEATHING IS REQUIRED TO MEET MINIMUM REQUIREMENTS
 OF FBC R TABLE 803.1.
  
 4. 6D NAILS SPECIFIED ON SHEET 3, DOES NOT MEET MINIMUM
 SHEATHING REQUIREMENTS, FBC R803.2.3.1.
  
 5. THE ENGINEER'S SEAL REQUIRES A DATE,
 FAC61G15-23.002.
  
 6. CERTIFICATE OF AUTHORIZAITON REQUIRED TO PRACTICE
 ENGINEERING THROUGH A COMPANY, FS471. TRUSS ENGINEERING
 INCLUDES "RICHARD WEINGARDT CONSULTANTS."
  
 7. ALL INFORMATION REQUIRED BY FAC61G15-23.002 ON EACH
 SHEET (TRUSS ENGINEERING).
  
 8. TRUSS ENGINEERING DESIGN SPECIFIES IBC, PLEASE
 REVISE TO GOVERNING CODE.
  
 9. ROOF PERMIT REQUIRED.
  
 10. PLEASE INCLUDE DISTANCE FROM EXISTING HOUSE TO
 PROPOSED NEW STRUCTURE, FBC R302.1.
  
 11. IT IS NOT CLEAR HOW THE DOOR WILL COMPLY WITH FBC
 R311.4.4. IS THIS DOOR OPERABLE FROM THE INSIDE?
  