2009-06-15 09:45:33RESIDENTIAL (R2) RE-ROOF, BUILDING REVIEW CHECKLIST.
 2007 FBC WITH 2009 REVISIONS.
  
 1- PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS FOR
 NAIL ENHANCING AT PERIMETER AND CORNER AREAS AS
 REQUIRED BY GENERAL LIMITATION #7 ON SHEET 14 OF NOA
 07-1018.10 SUBMITTED.
 ***NOTE: ACCORDING TO 2009 REVISIONS TO FBC 2007 THIS
 BUILDING IS LOCATED ON EXPOSURE "C". DESIGN
 PROFESSIONAL TO HAVE THIS EXPOSURE IN CONSIDERATION
 WHEN DOING THE RAS 117 CALCULATIONS.
  
 2- CLEARLY IDENTIFY WHICH APPROVED ASSEMBLY IS GOING TO
 BE INSTALLED TO VERIFY COMPLIANCE WITH THE CALCULATED
 DESIGN PRESSURES. NOA SUBMITTED SHOWS TWO DIFFERENT
 ASSEMBLIES. ONE ON PAGE 7 AND ONE ON PAGE 9. SELECT
 ONLY ONE ASSEMBLY AND PROVIDE RESPECTIVE RAS 117
 CALCULATIONS.
  